DCA-220SSVU (50 Hz) — OPERATION AND PARTS MANUAL — REV. #0 (04/18/06) — PAGE 37

1

DCA-220SSVU (50 HZ)— GENERATOR START-UP PROCEDURE (MANUAL)

Figure 47. Voltage Adjust Control Knob

Figure 48. Ammeter

(No Load)

8. The ammeter (Figure 48) will

indicate

zero amps with no load

applied. When a load is applied, the
ammeter will indicate the amount of
current that the load is drawing from
the generator.

7. The generator's AC-voltmeter (Figure 47) will display the

generator’s output in VOLTS. If the voltage is not within
the specified tolerance, use the voltage adjustment
control knob (Figure 47) to increase or decrease the
desired voltage.

Figure 46. Voltmeter

Figure 45. Frequency Meter (Hz)

6. The generator's frequency meter (Figure 45) should be

displaying the 60 cycle output frequency in HERTZ.

Figure 51. Engine

Tachometer Gauge

11. The

tachometer gauge (Figure 51)

will indicate the speed of the engine
when the generator is operating.
Under normal operating conditions
this speed is approximately 1600
RPM’s.

10. The

coolant temperature gauge

(Figure 50) will indicate the
coolant temperature. Under
normal operating conditions the
coolant temperature should be
between 165 and 203 degrees
Fahrenheit (

Green Zone).

Figure 50. Coolant

Temperature Gauge

9. The engine oil pressure gauge

(Figure 49) will indicate the oil
pressure

of the engine. Under

normal operating conditions the oil
pressure is approximately 44 to 73
psi. (303~503 kPa). When starting
the genera

Figure 49. Oil

Pressure Gauge

Figure 52. Main, Aux. and GFCI

Circuit Breakers (ON)

12. Place the

main, GFCI, and aux. circuit breakers in the

ON position (Figure 52).

13. Observe the generator's ammeter

(Figure 53) and verify it reads the
anticipated amount of current with
respect to the load. The ammeter
will only display a current reading if
a load is in use.

Figure 53. Ammeter

(Load)

14. The generator will run until manually stopped or an

abnormal condition occurs.