OTHER ELECTRICAL SPECIFICATIONS
Electrical Specifications
Input Voltage (AC Mode Function)
120VAC ± 15 VAC; 225 VAC ± 35VAC
Input Frequency Deviation for Synchronization
± 5%
Inrush Current
1.5xRated
Surge Protection
3 way, meets IEEE STD 587
RFI/EMI Filtering
Both Common & Normal Modes
Transfer
120VAC Units
220VAC Units
Brownout Transfer
105VAC
190VAC
Brownout AC Return
110VAC
200VAC
Over-voltage Transfer
135VAC
260VAC
Over-voltage AC Return
130VAC
250VAC
Transfer Speed
2ms Maximum
Inverter Crest Factor (Non-Linear Load)
3:1
Inverter Waveform
Synchronized Computer Grade Sinewave
Harmonic Distortion
Less than 3% THD at full linear load
Inverter Voltage Regulation
Static
± 3%
Dynamic
± 5% with 50% Linear Step Load Change
Inverter Frequency Regulation
0.5%
DC-to-AC Efficiency (Full Load)
80%
Overload/Short Circuit Protection
Yes, Electronic and Fuse
Discharged Battery Recharge Time
8 Hours (95% of Full Charge )
PHYSICAL SPECIFICATIONS
Physical Specifications
Model
Net Weight (LBS)
Shipping Weight (LBS)
Dimensions (L x W x H) (In.)
AT650
36.0
39
16.5 x 6.5 x 9.7
AT800
42.7
46
18.1 x 6.5 x 9.7
AT1200
62.4
67
19.0 x 7.9 x 13.3
AT1600
77.3
82
19.0 x 7.9 x 13.3
AT2300
92.1
96
21.7 x 7.9 x 13.9