Electrical specifications – Minuteman UPS AT800 User Manual
Page 5
3
Route unit power-cords so it cannot be walked on or damage.
ELECTRICAL SPECIFICATIONS
Electrical Specifications
Rated Output
Model
VA
Watts
Freq.
HZ
Input
VAC/A
Output
VAC/A
Battery
System
VDC
Back Up
Full Load
Time
(Min)
Half Load
Max Heat
Dissipation
BTU/HR
AT650
650
455
60
120/6.0
120/5.4
24
6
15
311
GS650
650
455
50
220/3.3
220/3.0
24
6
15
311
AT800
800
560
60
120/7.4
120/6.7
48
8
20
382
GS800
800
560
50
220/4.0
220/3.6
48
8
20
382
AT1200
1200
840
60
120/11.1
120/10.0
48
7
18
573
GS1200
1200
840
50
220/6.1
220/5.5
48
7
18
573
AT1600
1600
1120
60
120/14.8*
120/13.3*
72
8
20
765
GS1600
1600
1120
50
220/8.1
220/7.3
72
8
20
765
AT2300
2300
1610
60
120/21.3
120/19.2
72
4
10
1099
GS2300
2300
1610
50
220/11.6
220/10.5
72
4
10
1099
* Input/Output specifications above for model AT1600 are applicable when a 20-ampere power
plug (NEMA 5-20P) is utilized (non-standard). For a NEMA 5-15P plug (standard), derate input to
120VAC/12 Amperes and derate output in "AC Normal" mode only to 120VAC/10.8 Amperes.