beautypg.com

Electrical specifications – Minuteman UPS AT800 User Manual

Page 5

background image

3

Route unit power-cords so it cannot be walked on or damage.

ELECTRICAL SPECIFICATIONS

Electrical Specifications

Rated Output

Model

VA

Watts

Freq.

HZ

Input

VAC/A

Output

VAC/A

Battery

System

VDC

Back Up

Full Load

Time

(Min)

Half Load

Max Heat

Dissipation

BTU/HR

AT650

650

455

60

120/6.0

120/5.4

24

6

15

311

GS650

650

455

50

220/3.3

220/3.0

24

6

15

311

AT800

800

560

60

120/7.4

120/6.7

48

8

20

382

GS800

800

560

50

220/4.0

220/3.6

48

8

20

382

AT1200

1200

840

60

120/11.1

120/10.0

48

7

18

573

GS1200

1200

840

50

220/6.1

220/5.5

48

7

18

573

AT1600

1600

1120

60

120/14.8*

120/13.3*

72

8

20

765

GS1600

1600

1120

50

220/8.1

220/7.3

72

8

20

765

AT2300

2300

1610

60

120/21.3

120/19.2

72

4

10

1099

GS2300

2300

1610

50

220/11.6

220/10.5

72

4

10

1099

* Input/Output specifications above for model AT1600 are applicable when a 20-ampere power
plug (NEMA 5-20P) is utilized (non-standard). For a NEMA 5-15P plug (standard), derate input to
120VAC/12 Amperes and derate output in "AC Normal" mode only to 120VAC/10.8 Amperes.