MITSUBISHI ELECTRIC ETH-1000 User Manual
Page 14
3-8
3.4 Configuring the External Ethernet Module in the iQ System
When application requires, an external Ethernet module can be added to the system and communicating to
the iQ CPU. This section describes the configuration of a QJ71E71-100 module to be used in the
communication with a CLX through the ICC ETH-1000 gateway.
1. Select the Network Parameter-> Ethernet/CC IE/MELSECNET on the Project Tree which will open
the parameter setting window.
a. Select the Network Type to be “Ethernet.”
b. Set up appropriate Network, Group, and Station numbers depending on the application
network topology. In the verification system, the Network Number is set to be 1, the Group
Number is set to 1, and the Station Number is set to 2.
c. Set the Mode to “On Line.”
d. Click “Operation Setting” to go to the next steps.