beautypg.com

5example of system configuration – MITSUBISHI ELECTRIC PAC-YG60MCA User Manual

Page 4

background image

3

5

Example of System Configuration

Note:

• For the shield ground of the M-NET centralized control line for central control, use single-point grounding at the power unit for

the transmission line.

However, when supplying electric power to the M-NET centralized control line from the R410A series outdoor unit without using

a power supply unit for the transmission line, use single-point grounding at the TB7 of that outdoor unit.

Furthermore, when connecting this device to the M-NET indoor control line, use grounding at the TB3 for each outdoor unit

system.

• Connecting an Uninterruptible power supply (UPS) to the 24 VDC power supply is recommended in order to prevent the loss of

pulse data in the event of a power failure.

If a UPS cannot be connected, try to make the AC power supply to the 24 VDC power supply as much same as the power supply

line to the meters.

• This device does not support level meters. To use a level meter, incorporate a Converter circuit externally and convert to pulse

input.

• If this device is connected to an M-NET indoor control line and the outdoor unit is down because, for example, the power supply

is interrupted for servicing or there is a failure, the PI controller cannot be controlled from the system controller.

TB3

M-NET

M-NET

LAN

TB7

Centralized control line

Indoor control line

PI controller

G-50A or GB-50A

G(B)-50A Web

or TG-2000A

Uninterruptible

power supply

(UPS)

Watt-hour meter with

pulse transmitter, etc.

Maximum of 5 units (total of 20 channels) per G(B)-50A

However, the number of units that can be connected to a

G(B)-50A is up to 50 including this device, an indoor unit,

Lossnay unit, etc.

* For the number of units that can be connected when

controlling this device with TG-2000A, refer to the

instruction manual for TG-2000A.

* This figure omits the power supply line and only shows the transmission line.

Power supply unit

PAC-SC50KUA

PI controller

24 VDC

power supply

Up to 4 contacts

Watt-hour meter with

pulse transmitter, etc.

Uninterruptible

power supply

(UPS)

24 VDC

power supply

Up to 4 contacts

City Multi