beautypg.com

Advanced operations – MGE UPS Systems AmpMeter PDU User Manual

Page 44

background image

4. Advanced Operations

Displaying trap configuration information

The Show Traps command displays information about all traps.

To display trap information:

At the AmpMeter PDU: prompt, type

show traps

and press

Enter

.

Example

The following command requests trap configuration information:

AmpMeter PDU: show traps
Tower trap configuration:
Tower Tower Status
ID Name Trap
.A Florida_HQ_1 ON
.B Florida_HQ_2 ON
More (Y/es N/o): y
Input feed trap configuration:
Input Input Status Load High
Feed ID Feed Name Trap Trap Thresh
.AA HQ_1_Infeed_A ON ON 255 A
.BA HQ_2_Infeed_A ON ON 255 A
More (Y/es N/o): y
Environmental Monitor .A trap configuration:
Name: Florida_HQ_1
Status Trap: ON
Temperature/Humidity Sensor .A1 Temperature/Humidity Sensor .A2
Name: Temp_Humid_Sensor_A1 Name: T/H2_Florida_HQ_1
Status Trap: ON Status Trap: ON
Temp Trap: ON Temp Trap: ON
Low: 0 Deg.C Low: 0 Deg.C
High: 127 Deg.C High: 95 Deg.C
Humid Trap: ON Humid Trap: ON
Low: 5 % RH Low: 0 % RH
High: 100 % RH High: 100 % RH

Page 44 - 301-0399-3 Rev B.