Electrical work – MITSUBISHI ELECTRIC Mr. Slim PLA-A-AA User Manual

Page 9

background image

9

6. Electrical work

6.1.3. K-control application

The following connection patterns are available.
The outdoor unit power supply patterns vary on models.

1:1 System

* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.

A Outdoor unit power supply
B Wiring circuit breaker or isolating switch
C Outdoor unit
D Indoor unit/outdoor unit connecting cords
E Remote controller
F Indoor unit
G Indoor unit
H Indoor unit power supply

Simultaneous twin system

A Outdoor unit power supply
B Wiring circuit breaker or isolating switch
C Outdoor unit
D Indoor unit/outdoor unit connecting cords
E Remote controller
F Main indoor unit
G Sub indoor unit
H Indoor unit power supply
J Main indoor unit
K Sub indoor unit

*1. Max. 50 m, 165 ft
*2. The 10 m, 30 ft wire is attached in the remote controller accessory. Max. 500 m, 1500 ft
*3. The figures are NOT always against the ground.

Notes: 1. Wiring size must comply with the applicable local and national code.

2. Use copper supply wires.
3. Use wires rated 300V or more for the power supply cables.
4. Install an earth longer than other cables.

Indoor unit model
Indoor unit power supply
Minimum circuit ampacity
Maximum rating of overcurrent protective device

Indoor unit power supply
Indoor unit power supply earth

Indoor unit-Outdoor unit

*1

Indoor unit earth
Remote controller-Indoor unit

*2

Indoor unit L1-L2

*3

Indoor unit-Outdoor unit S1-S2

*3

Indoor unit-Outdoor unit S1-S3

*3

Remote controller-Indoor unit

*3

PLA-A12, 18, 24, 30

PLA-A36, 42

Single 208/230 V, 60 Hz

Single 208/230 V, 60 Hz

1 A

2A

15A

15A

2

× Min. AWG16

2

× Min. AWG16

1

× Min. AWG16

1

× Min. AWG16

H/P: 3

× AWG22 (polar)

H/P: 3

× AWG22 (polar)

C/O: 2

× AWG22 (polar)

C/O: 2

× AWG22 (polar)

2

× AWG22 (Non-polar)

2

× AWG22 (Non-polar)

AC 208/230 V

AC 208/230 V

DC12V

DC12V

DC12V

DC12V

DC12V

DC12V

Circuit

rating

Wir

ing

Wire No

. ×

siz

e

S1
S2

L1
L2

GR

GR

1
2

L1
L2

S1
S2
S3

S3

A

B

C

H

D

B

E

F

S1
S2

L1
L2

GR

GR

1
2

L1
L2

S1
S2
S3

S3

A

B

C

H

D

B

E

G

1

SW5

Set the DIP switch of the indoor
unit control board.

SW5–1 : ON SW5–2, 3 : OFF

2 3

1

SW5

Set the DIP switch of the indoor
unit control board.

SW5–1, 2 : ON SW5–3 : OFF

2

3

S1
S2

L1

GR

L2

1
2

L1
L2

GR

GR

S1
S2
S3

1
2

L1
L2

S1
S2
S3

S3

A

B

C

D

H

B

E

F

G

S1
S2

1
2

S1
S2
S3

1
2

S1
S2
S3

S3

A

B

C

D

H

B

E

J

K

L1

L2

GR

L1

L2

GR

L1

L2

GR

1

SW5

Set the DIP switch of the indoor
unit control board.

SW5–1 : ON
SW5–2 : OFF
SW5–3 : OFF

2 3

1

SW5–1 : ON
SW5–2 : OFF
SW5–3 : ON

2

3

G Main indoor

H Sub indoor

1

SW5

Set the DIP switch of the indoor
unit control board.

SW5–1 : ON
SW5–2 : ON
SW5–3 : OFF

2

3

1

SW5–1 : ON
SW5–2 : ON
SW5–3 : ON

2 3

K Main indoor

L Sub indoor

OFF

ON

SW5–1

A–CONTROL

K–CONTROL

SW5–2

heat pump models

cooling only models

SW5–3

MAIN

SUB

S1

S2

S3

L1

L2

GR

BLUE

BLUE

YELLOW

YELLOW

CND

CND

ORANGE

CN3C

BLUE

CN30

BLACK

S1

S2

S3

L1

L2

GR

BLUE

YELLOW

YELLOW

BLUE

CND

CND

ORANGE

CN3C

BLUE

CN30

CN30

CN30

CN3C

CN3C

BLACK

INDOOR UNIT
CONTROL BOARD

INDOOR UNIT
CONTROL BOARD

Connectors

To change to the K-control,
make sure to change the
connectors as shown in the
figure.

BLUE

BLUE

BLACK

BLACK

BLUE

BLUE

BLACK

BLACK

To change to K-control, set the DIP switch (SW5) of the indoor unit control board as
shown in the above figure and change the electric wiring of the indoor unit as shown
in the right figure.
Set up Dip switch after turning off Power supply switch.
Be careful that setting the DIP switch (SW5) of the indoor unit control board varies
between the heat pump models and cooling models of the outdoor unit.

DIP switch (SW5)

* There are three types of labels (labels A, B, and C). Affix the appropriate labels to

the units according to the wiring method.

}

Dip switch SW5-2 and SW5-3 is effective only
when Dip switch SW5-1 (K-CONTROL) is ON.

* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.

BG79U795H01_en.pm6

05.12.1, 9:48 AM

9