Miller Electric DWF3 User Manual
Page 20

SECTION 3
OPERATION
OM-179 078
3-4
Figure 3.3, REMOTE WIRING CABLE
The remote start function requires a signal of +5 to 24 VDC. This signal is applied to pin C of J3. The common
is from the DWF–3 (this signal is optically isolated from the DWF–3); therefore, the signal common need not
be attached to the control unit ground. This signal would normally come through the normally open contacts of
a relay that is activated at the start of a weld cycle, for example, the Seam Tracker interface relay.
The inhibit function requires a signal of +5 to 24 VDC applied to pin E of J3, and common connected to pin G of
J3. The inhibit signals are optically isolated from the DWF–3 control unit, and the common need not be
connected to the control unit ground.
Figure 3.4, REMOTE START WIRING
- OM-2241 (32 pages)
- ICE-27C (36 pages)
- Arc Welding Power Source (4 pages)
- INVISION 456 CC (44 pages)
- Welder (132 pages)
- SS-75D12 (44 pages)
- Load Bank LBP-350 (2 pages)
- OM-193 084E (36 pages)
- 750MPa (2 pages)
- APT-1000 (20 pages)
- OM-220 390F (48 pages)
- 271 (48 pages)
- Welding (32 pages)
- DC (72 pages)
- OM-129 (70 pages)
- XLi (24 pages)
- S-64 (36 pages)
- ICE-27T (36 pages)
- PipePro 304 (76 pages)
- AA40GBU (28 pages)
- D-64 (40 pages)
- Auto Arc XLT 165 (48 pages)
- 185 DX (56 pages)
- S-32S (4 pages)
- Big 40 DC/TIG 55500 A (8 pages)
- Big Blue 600D (60 pages)
- Millermatic 140 (60 pages)
- pmn (36 pages)
- LMSW Series (2 pages)
- 1250 (46 pages)
- Trailblazer Pro 350 D (8 pages)
- TS (76 pages)
- S-22P12 (28 pages)
- 602 (40 pages)
- Axcess 300 (56 pages)
- MOG-400 (40 pages)
- WC-24 (20 pages)
- Big Blue 502P (64 pages)
- Dimension 1000 (44 pages)
- DS-74DX12 (52 pages)
- 350 VS (36 pages)
- 24A (32 pages)
- GA-16C (12 pages)
- Big Blue 502D (116 pages)
- OM-229 038D (36 pages)