Minuteman UPS ED6000T User Manual
Page 8
12
3.2.
Installation Placement
This UPS system is intended to be install in a temperature controlled
environment that is free of conductive contaminants. Select a location, which
will provide good air circulation for the UPS at all times. Keep at least 12
inches (30cm) clearance from the rear panel of the UPS to the wall. Avoid
locations near heating devices, water or excessive humidity, or where the
UPS is exposed to direct sunlight. Route power cords so they cannot be
walked on or damaged.
ENVIRONMENTAL
Operating Temp (max)
0 to 40ºC (+32 to +104ºF) <2000m (<+6700 ft)
0 to 35ºC (+32 to +95ºF) at 3000m (+10,000 ft)
Storage Temp
-15 to +45ºC (+5 to +113ºF)
Operating/Storage Humidity
30 - 90% Non-Condensing
Storage Elevation
0 to 15,000m (0 to +50,000 ft)
3.3.
Storage Instruction
For extended storage with moderate climates, the batteries should be
charged for 12-hours every 3 months. Repeat this procedure every 2 months
under high temperature environments.
13
3.4.
Installation of the Caster Covers
3.4.1 Lock the casters so that the unit will not move.
3.4.2 Step 1: There are two A1 cover plates, one for each side of the unit. Insert
the A1 cover plates into the slots and slide towards the rear of the unit.
3.4.3 Step 2: There are two A2 cover plates, one for the front of the unit and one
for the rear of the unit. Insert the A2 cover plates into the slots and push
downwards toward the floor.
3.4.4 Step 3: There are four retaining screws S1. Install the S1 retaining screws
into the A2 cover plates.
3.4.5 Step 4: There is one A3 cover plate. Insert the A3 cover plate into the holes
on the A2 cover plate on the front of the unit and press firmly.