beautypg.com

Minuteman UPS ED6000T User Manual

Page 10

background image

16

3.5.1.1.4 Configuration # 3:

Output: One 208VAC 6KVA circuit. Total output load not to exceed 6KVA.

1. Connect a jumper wire from L22 to N21.
2. Circuit1 (208VAC): L23 - L1, N22 - L2, G2 - Ground.














3.5.1.1.5 Configuration # 4:

Output: One 240VAC 6KVA circuit. Total output load not to exceed 6KVA.

1. Connect a jumper wire from L22 to N21.
2. Circuit1 (240VAC): L21 - L1, N22 - L2, G2 - Ground.


















17

3.5.1.1.6 Configuration # 5:

Output: Two 120VAC circuits (3KVA max load per circuit). and one 208VAC
6KVA circuit. Total combined output load not to exceed 6KVA.

1. Connect a jumper wire from L22 to N21.
2. Circuit1 (120VAC): L22 - Line, N22 - Neutral, G2 - Ground.
3. Circuit2 (120VAC): L21 - Line, N21 - Neutral, G2 - Ground.
4. Circuit3 (208VAC): L23 – L1, N22 – L2, G2 - Ground.














3.5.1.1.7 Configuration

#6:

Output: Two 120VAC circuits (3KVA max load per circuit) and one 240VAC
6KVA circuit. Total combined output load not to exceed 6KVA.

1. Connect a jumper wire from L22 to N21.
2. Circuit1 (120VAC): L22 - Line, N22 - Neutral, G2 - Ground.
3. Circuit2 (120VAC): L21 - Line, N21 - Neutral, G2 - Ground.
4. Circuit3 (240VAC): L21 – L1, N22 – L2, G2 - Ground.














This manual is related to the following products: