Diagnostic Error Codes for 2KVA, 3KVA, 5KVA, 7KVA units
Error
Description
E00
System ROM checksum error.
E01
System RAM data read/write error.
E02
System EEPROM data read/write error.
E03
Communication fail between CPU & DSP
E05
Temperature over
100
o
C
.
E07
Battery voltage is over specification (AC mode).
E08
Input voltage fail (Outside of safe operating range & cold start disable).
E10
Configure SW1 is set position “OFF”.
E11
AC Mode input out of range during normal startup.
E12
Battery voltage out of range during cold start.
E14
DC bus voltage out of range during cold start.
E15
Output/input voltage difference out of 3.125% (AC tracking mode).
E16
Output/setting voltage difference out of 3.125% (DC mode).
E17
Input frequency fail (Out of 45 ~ 65 Hz) & cold start disable.
E22
DC bus voltage out of range -85% or +12%
E23
Difference between DC bus is more then 70Vdc.
E25
Input / Output frequency difference out of 1Hz during AC mode normal
E26
Battery voltage low (2K-57V, 3K-76V, 5K-190V, 7K-228V) out of range (DC mode)
E32
RMS current over 100%
E33
Voltage difference more than 10% between setting and output
E40
Temperature over 80
o
C
.
E42
Thermal sensor dead.
E53
Battery test error.(battery may be bad)
E54
Line-Neutral connection error.
E60
Transfer fail during AC Bypass to AC Mode
E63
Transfer fail during Battery Mode to normal AC mode.
E67
DC bypass to Battery mode time out in soft start.
E68
AC bypass to Normal mode time out in soft start.
E69
In/out Sync lasts too long.
E78
DIP Switch setting error(output voltage setting).
E80
DSP initial state data transfer error (clear 0ffh).
E81
No response when send data to DSP.
E82
DSP initial state data transfer error (55,aa,version).
E83
Data lost (every cycle received data less than 20 and more than 60 times).
E84
Input voltage break at bypass mode.