PAGE 28 — DCA-25SSIU2 (50 HZ)— OPERATION AND PARTS MANUAL — REV. #0 (03/11/05)

Figure 22. Voltage Selector Switch 240/139V

Three-Phase Position

DCA-25SSIU2 (50 HZ)— OUTPUT TERMINAL PANEL CONNECTIONS

UVWO Terminal Output Voltages

Various output voltages can be obtained using the

Output

Terminal Lugs.. The voltages at the terminals are depen-
dent on the position of the

Voltage Selector Switch and the

adjustment of the

Voltage Regulator Control Knob.

Remember the voltage selector switch determines the

range

of the output voltage. The voltage regulator (VR) allows the
user to increase or decrease the selected voltage.

3Ø-200/115 Output Terminal Lug Voltages

1. Place the voltage selector switch in the 3Ø 240/139

position as shown in (Figure 22).

Figure 23. Output Terminal Lugs

3Ø-220/127V Three Phase Connections

2. Connect the load wires to the

Output Terminal Lugs as

shown in (Figure 23).

3. Turn the voltage regulator knob (Figure 24) clockwise to

increase voltage output, turn counterclockwise to
decrease voltage output.

3Ø 200V/1Ø115V Output Terminal Lug Voltages

1. Place the voltage selector switch in the 3Ø 240/139

position as shown in Figure 25.

Figure 24. Voltage Regulator Knob (139V/240V)

Use this position for
3Ø-200 or 1Ø115V.

2. Connect the load wires to the

Output Terminal Lugs as

shown in Figure 26.

NOTE

To achieve a 3Ø 200V output
the voltage selector switch
must be in the 3Ø-240/139
position and the voltage
regulator must be adjusted to
200V.

Figure 26. Output Terminal Lugs

3Ø-200/115V Connections

Figure 25. Voltage

Selector Switch 240/139V

Three-Phase Position

3. Turn the voltage regulator knob (Figure 25) clockwise to

increase voltage output, turn counterclockwise to
decrease voltage output.