10-3.Outdoor low pressure and outdoor unit current

1. 07-class unit in single operation

NOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system).

The converted score against the traditional unit system can be gotten according to the formula below.

1(MPa • G) =10.2(kgf/

f

f

• G)

(1) COOL operation

1

Both indoor and outdoor units are under the same

temperature/humidity condition.

Dry-bulb temperature(°C)

Relative humidity(%)

20

50

25

60

30

70

1.Set emergency switch to COOL or HEAT.The switch is locat-

ed on indoor unit.

2.Press emergency run ON/OFF button.
3.Compressor starts running at rated frequency.
4.Indoor fan runs at HI speed and continues for 30 minutes.
5.To cancel this operation,press emergency run ON/OFF button

or any button on remote controller.

Indoor

Outdoor

Set air flow to Hi speed.
Inverter output frequency is 45Hz.

(2) HEAT operation

DB(°C) 20.0

WB(°C) 14.5

DB(°C) 2

7

15

20.0

WB(°C) 1

6

12

14.5

0

5

10

15

20

25

4

5

6

7

8

9

10

Ambient temperature(

:

)

45Hz

Outdoor unit current (A)

Ambient temperature(

:

)/ Ambient humidity(%)

Ambient temperature(

:

)/ Ambient humidity(%)

Outdoor low pressure

(MPa•Gauge)

(kgf/

F

•Gauge)

Outdoor unit current (A)

15

20

25

30

35

0.2

0.3

0.4

0.5

0.6

0.7

0.8

(

;

)

(%)

33Hz

15 20

25

30 35

3

4

5

6

7

8

9

(

;

)

(%)

33Hz

8

7

6

5

4

3

2

2

Air flow speed : HI

3

Inverter output frequency : 33Hz