10-3.Outdoor low pressure and outdoor unit current
1. 07-class unit in single operation
NOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/
f
f
• G)
(1) COOL operation
1
Both indoor and outdoor units are under the same
temperature/humidity condition.
Dry-bulb temperature(°C)
Relative humidity(%)
20
50
25
60
30
70
1.Set emergency switch to COOL or HEAT.The switch is locat-
ed on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at rated frequency.
4.Indoor fan runs at HI speed and continues for 30 minutes.
5.To cancel this operation,press emergency run ON/OFF button
or any button on remote controller.
①
➁
Indoor
Outdoor
Set air flow to Hi speed.
Inverter output frequency is 45Hz.
➂
(2) HEAT operation
DB(°C) 20.0
WB(°C) 14.5
DB(°C) 2
7
15
20.0
WB(°C) 1
6
12
14.5
0
5
10
15
20
25
4
5
6
7
8
9
10
Ambient temperature(
:
)
45Hz
Outdoor unit current (A)
Ambient temperature(
:
)/ Ambient humidity(%)
Ambient temperature(
:
)/ Ambient humidity(%)
Outdoor low pressure
(MPa•Gauge)
(kgf/
F
•Gauge)
Outdoor unit current (A)
15
20
25
30
35
0.2
0.3
0.4
0.5
0.6
0.7
0.8
(
;
)
(%)
33Hz
15 20
25
30 35
3
4
5
6
7
8
9
(
;
)
(%)
33Hz
8
7
6
5
4
3
2
2
Air flow speed : HI
3
Inverter output frequency : 33Hz