Master Bilt 19-14009 User Manual
Page 6

Operating Instructions for Master-Bilt Alarm/Light Module (19-14009)
1598003200
6
13. PARAMETER MAP
LABEL
DESCRIPTION
VALUE
LEVEL
RANGE
ot
Thermostat probe
calibration
0 Pr2
[-12,0°C <> 12,0°C] [-
21°F <> 21°F]
CF
T° measurement unit
F
Pr2
°C(0) - °F(1)
rES
Resolution (only °C)
in
Pr2
dE(0) - in(1)
UT
Display update
60
Pr2
0 <> 255 (s)
OnF
Off function enabling
y
Pr2
n(0) - Y(1)
ALU
High Tempalarm setting
50 Pr1
°C[ ALL <> 150,0°] °F[
ALL <> 302°]
ALL
Low Temp alarm setting
30 Pr1
°C[ -50.0° <> ALU] °F[-
58 <> ALU]
AFH
Temp alarm differential
2 Pr2
[0,1°C <>25,5°C] [1°F
<> 45°F]
ALd
Temp alarm delay
30
Pr1
0 <> 255 (min.)
dAo
Delay of Temp alarm at
start-up
1.3 Pr2
0 <> 24H0(144)
EdA
Alarm delay at the end
of defrost
30 Pr2
0 <> 255 (min.)
dot
Delay of Temp alarm
after closing the door
15 Pr2
0 <> 255 (min.)
LHt
Light timer
15
Pr1
0 <> 255 (min.)
doA
Open door alarm delay
15
Pr1
0 <> 255 (min.)
OA1
First relay configuration
ALr
Pr2
ALr(0) - LHt(1) - OnF(2)
oA2
Second relay
configuration
LHt Pr2
ALr(0) - LHt(1) - OnF(2)
AOP
Alarm relay polarity
oP
Pr2
OP - CL
i1P
Digital input 1 polarity
oP
Pr2
OP(0) - CL(1)
i1L
Door switch to turn light
ON
y Pr2
n(0) - Y(1)
i1F
Digital input 1 operating
mode
dor Pr2
EAL(0) - dor(1) - dEr(2)
- LHt(3)
i2P
Digital input 2 polarity
cL
Pr2
OP(0) - CL(1)
i2F
Digital input 2 operating
mode
PA
n
Pr2
EAL(0) - Pan(1) -
dFr(2) - LHt(3)
did
Time interval/delay for
digital input alarm
0 Pr2
0 <> 255 (min.)
tbA
Alarm relay disabling
n
Pr2
n(0) - Y(1)
PbC
Kind of probe
ntc
Pr2
PtC(0) - ntC(1)
dP1
Real T° Probe 1
Pr2
(probe value)
rEL
FW release
Pr2
read only
Ptb
Parameter map
Pr2
read only