According to european standards – MGE UPS Systems 12280 kVA User Manual
Page 5
MGE UPS SYSTEMS
CleanWave - Installation and user manual
Page 5/13
Version 2.1 - 21/04/05 - (JME)
2.2. R
ANGE
The following table summarises the characteristics of the different products of the range (at 400V,
50/60Hz).
Minimum sections
1
TYPE
Power.
I
phase
max
I
neutral
Max
Total
losses
max
Phases
Neutral (N)
Earth (PE)
( PEN
2
)
[kVA]
[A]
[A]
[W]
[mm²]
[mm²]
[mm²]
[mm²]
CleanWave-12
12
16
29
176
2.5
6
2.5
6
CleanWave-18
18
24
43
219
4
10
4
10
CleanWave-30
30
40
72
359
10
25
10
25
CleanWave-40
40
56
101
452
16
35
16
35
CleanWave-55
55
80
144
538
25
2x 25
16
2x 25
CleanWave-90
90
128
231
616
50
2x 50
25
2x 50
CleanWave-140
140
201
361
972
95
2x 95
50
2x 95
CleanWave-180
180
264
476
1212
150
2x 150
95
2x 150
CleanWave-220
220
321
577
1565
2x 95
2x 185
95
2x 185
CleanWave-280
280
401
722
1568
2x 95
2x 240
95
2x 240
Table 4
1
According to European standards
2
If common conductor for neutral and earth (PEN conductor)
- Pulsar EX 1000 (28 pages)
- 4.5 kVA (32 pages)
- 1100 (196 pages)
- EPS 8000 (54 pages)
- S EXB 2500 (22 pages)
- Pulsar Extreme 3200C (28 pages)
- ESV 22+Rack (24 pages)
- GES-801L (22 pages)
- Comet EX 7 RT 3:1 (38 pages)
- EX 11RT (72 pages)
- Galaxy PW (44 pages)
- 3 (34 pages)
- Pulsar TM 30 (18 pages)
- 22+ EB 22 (44 pages)
- 1500C (28 pages)
- Rackmount PDU (36 pages)
- Pulsar Esprit 313.5 kVA (6 pages)
- EX-5 (76 pages)
- 30A (30 pages)
- AmpMeter PDU (52 pages)
- EX30 (106 pages)
- 1100 Tower (36 pages)
- 40-75KVA (56 pages)
- 2000 (34 pages)
- 4000 RT (38 pages)
- Pulsar EXtreme C UPS 1500 VA (4 pages)
- FlexPDU 6 AUS (12 pages)
- POWER-SURE 700 (52 pages)
- 250A (34 pages)
- EX 1000 (28 pages)
- EX7 (18 pages)
- EX30Rack (24 pages)
- 40-150kVA (56 pages)
- 100 (32 pages)
- Uninterruptible Power Provider (4 pages)
- EPS 7000 (62 pages)
- 300 (6 pages)
- EX10Rack (22 pages)
- 500 (4 pages)
- EPS 6000 (84 pages)
- S3 (64 pages)
- EX RT CLA (6 pages)
- 3000 (32 pages)
- 3.5 to 21 kVA N+1 (54 pages)