I/O MODULES DESCRIPTION
32
CIO Remote CAN Digital I/O Module
GEK-106465A
5.2. CONTROL
SETTINGS FOR INPUTS/OUTPUTS
This section explains the settings related to CIO inputs/outputs. Modification of these values is performed using the
master unit communication software, EnerVista F650Setup for F650, or GE-CONF for F600.
5.2.1.
INPUT/OUTPUT BOARDS SETTINGS
Settings relative to I/O boards are described in table 5-1:
TABLE 5-1 I/O BOARD SETTINGS
SETTING
HMI
DEFAULT
RANGE
STEP
16 INP + 8OUT
8 INP + 8OUT +
SUPV
I/O board type (available only for
CIO modules)
I/O Board_X Type
NONE
NONE
N/A
Input activation voltage threshold
Group A
Voltage Threshold A_X
80
0 – 255 V
1 V
Input activation voltage threshold
Group B
Voltage Threshold B_X
80
0 – 255 V
1 V
Debounce time Group A
Debounce Time A_X
15
1 – 50 ms
1 ms
Debounce time Group B
Debounce Time B_X
15
1 – 50 ms
1 ms
POSITIVE-EDGE
NEGATIVE-EDGE
POSITIVE
Input type
Input Type_X_CCY POSITIVE
NEGATIVE
N/A
Input signal time delay
Delay Input
Time_X_CCY
0
0 – 60000 ms
1 ms
Output logic type
Output Logic_X_0Z POSITIVE
POSITIVE-
NEGATIVE
N/A
NORMAL
PULSE
Output type
Output Type_X_0Z NORMAL
LATCH
N/A
Output pulse length
Pulse Output
Time_X_0Z
0
0 – 60000 ms
1 ms
Being:
X
I/O board name, depending on the CIO model.
For the I/O board selection in the relay model, associated digits to each board type are as follows:
ASSOCIATED DIGIT
F650PC BOARD
SETTINGS
BOARD TYPE
0 NONE
None
1
16 INP+ 8OUT
Mixed
2
8 INP +8 OUT +SUPV
Supervision