Operating data – Guardian Technologies QT060 User Manual
Page 3

QT060
kW RATING
60
ENGINE SIZE
2.4 Liter Inline 4
GENERATOR OUTPUT VOLTAGE/KW - 60Hz
KW
AMP
CB Size
120/208V, 3-phase, 0.8 pf
60
208
250
120/240V, 3-phase, 0.8 pf
60
180
200
277/480V, 3-phase, 0.8 pf
60
90
100
GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Single phase or 208/240 3-phase
120
480V 3-phase
141
ENGINE FUEL CONSUMPTION
(Natural Gas) (Propane)
Natural Gas
Propane
(ft
3
/hr.)
(gal/hr.)
cu ft/hr
Exercise cycle
123
1.34
49.3
25% of rated load
267
2.7
101
50% of rated load
483
5.0
183
75% of rated load
672
7.0
255
100% of rated load
862
9.0
327
ENGINE COOLING
Air flow
(inlet air including alternator and combustion air)
ft
3
/min.
3,280
System coolant capacity
US gal.
2.5
Heat rejection to coolant
BTU/hr.
270,000
Max. operating air temp. on radiator
°C (°F)
60 (150)
Max. ambient temperature
°C (°F)
50 (140)
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz
cfm
180
SOUND EMISSIONS IN DBA
Exercising at 7 meters
65
Normal operation at 7 meters
72
EXHAUST
Exhaust flow at rated output 60 Hz
cfm
494
Exhaust temp. at muffler outlet
°F
1,050
ENGINE PARAMETERS
Rated synchronous RPM
60 Hz
3600
HP at rated KW
60 Hz
94
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration
3% for every 10 °C above - °C
25
1.65% for every 10 °F above - °F
77
Altitude Deration
1% for every 100 m above - m
915
3% for every 1000 ft. above - ft.
3000
OPERATING DATA
QT060
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings
apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is
no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.