MAINTENANCE PERFORMED BY
AUTHORIZED SERVICE FACILITIES

Before working on the generator, ensure the fol-

lowing:

• The AUTO/OFF/MANUAL switch is in the OFF

position.

• The 15A fuse has been removed from the con-

trol box.

• The 120VAC supply to the battery charger is

switched OFF.

EVERY THREE MONTHS

1. Check

battery

condition.

2. Inspect and test fuel system.
3. Check

transfer

switch.

4. Inspect

exhaust

system.

5. Check engine ignition system.
6. Check

fan

belts.

ONCE EVERY SIX MONTHS

1. Test Engine Safety Devices (low oil pressure, low

coolant level, high coolant temperature).

ONCE ANNUALLY

1. Test engine governor; adjust or repair, if needed.
2. Clean,

inspect

generator.

3. Flush

cooling

system.

FIRST 100 OPERATING HOURS

1. Change engine oil and oil filter. After initial

change, service engine oil and filter at 150 operat-
ing hours or six months, whichever comes first.

2. Retorque

cylinder

head.

3. Retorque intake and exhaust manifold.

EVERY 500 OPERATING HOURS

1. Service

air

cleaner.

2. Check

starter.

3. Check engine DC alternator.

EVERY 800 OPERATING HOURS

1. Retorque

cylinder

head.

2. Retorque intake and exhaust manifold.
3. Check

engine

compression.

4. Check

valve

clearance.

‹

‹

‹

‹

‹

‹

COOLING SYSTEM

Air intake and outlet openings in the generator com-
partment must be open and unobstructed for contin-
ued proper operation. This includes such obstruc-
tions as high grass, weeds, brush, leaves and snow.

Without sufficient cooling and ventilating air flow, the
engine/generator quickly overheats, which causes it
to shut down. (See the installation diagram.)

The exhaust system parts from this product get

extremely hot and remains hot after shutdown.
High grass, weeds, brush, leaves, etc. must
remain clear of the exhaust. Such materials may
ignite and burn from the heat of the exhaust
system.

OVERLOAD PROTECTION FOR ENGINE
DC ELECTRICAL SYSTEM

Engine cranking, start up and running are controlled
by a solid state Engine Controller circuit board.
Battery voltage is delivered to that circuit board via
a 15 amp fuse. These overcurrent protection devices
will open if the circuit is overloaded.

If a circuit breaker opens or a fuse element

melts, find the cause of the overload before
resetting the circuit breaker or replacing the
fuse.

CHECKING FLUID LEVELS

CHECK ENGINE OIL

Check engine crankcase oil level (Figure 10.1) at least
every 20 hours of operation, or prior to use.

• Remove oil dipstick and wipe dry with a clean, lint-

free cloth.

• Install oil dipstick, then remove again.
• Oil should be between FULL and ADD marks.
• If oil level is below the dipstick ADD mark, remove

oil fill cap-. Add the recommended oil to bring oil
level up to the FULL mark. DO NOT FILL ABOVE
THE “FULL” MARK. See “Engine Oil Recommen-
dations” for recommended oils.

‹