COLD WEATHER KIT

For cold climates, optional cold weather kit (part
number 0F6148) is recommended. The kit includes:

• Battery Warmer
• 4” Junction Box with hardware
• 6 qt. pack 5W-30 synthetic oil (engine)

RECONFIGURING THE FUEL SYSTEM

NOTE:

All models are configured for natural gas or LP
vapor from the factory.

To reconfigure the fuel system from NG to LP, follow
these steps:

1. Turn the main gas supply off.
2. Remove the carburetor fuel hose from the outlet

port (Port 1) of the demand regulator (Figure
6.2).

3. Remove the brass hose fitting from the outlet port

(Port 1) of the demand regulator.

4. Remove pipe plug from Port 2.
5. Install brass hose fitting into Port 2.
6. Install pipe plug into Port 1.
7. Connect carburetor gas hose to brass fitting.
8. Tighten all clamps and plugs.
9. Make sure fuel supply is of the proper pressure

and type for configuration.

‹

‹

10. Reverse the procedure to convert back to natural

gas.

11. The Dip switch inside the control panel must be

in the LP or NG position when switching to differ-
ent fuels.

Figure 6.2 — Reconfigure the Fuel System

NG FUEL SYSTEM

LP FUEL SYSTEM

Port 1

Port 2

FUEL HOSE

BRASS HOSE
FITTING

HOUSING
PORTS

OUT
PORT 2

PLUG

FUEL HOSE

BRASS HOSE
FITTING

HOUSING
PORTS

PLUG

OUT

PORT 1

NOTE:

Port 1 is for NG only and Port 2 is for LP vapor
only. No provision for dual fuel has been made.

DANGER

Serious injury or damage may occur if not con-

figured properly. Please consult an Authorized
Dealer with any questions.

TO
ALTERNATOR

NEUTRAL

GROUND

CIRCUIT
BREAKER

NEUTRAL

Ground Level
Concrete Slab

STUB-UP AREA

See Install Dwg for

Dimensions

CONTROL PANEL

GENERATOR
CONNECTION
BOX

FRAME RAIL

N1
N2
23
194

186

178

To Generator Control Panel

Utility In

Load
Out

Gen

N1
N2
23
194

183
178

120 Volt +
Neutral
Grd

Battery
Charger
Input

Transfer Switch

CIRCUIT BREAKER SIZE
KW VOLTS / AMPS LUG SIZE
20 240 1 Ø

100

#4 to 1/0

20 208 3 Ø

80

#4 to 1/0

4- # 14 GA
WIRES TO
GENERATOR
CONNECTION
BOX

TO GENERATOR
CONNECTION BOX

Figure 1 — Interconnections

6-2

Standby Generator Sets

Specifications

GenSpec013 Rev.

A 09/05