Cpc036 high static belt drive down shot, Cpc048 high static belt drive down shot, Cpc/h060 high static belt drive down shot – Goodman Mfg IO-354B User Manual
Page 22: Cpc/h072 high static belt drive down shot

22
APPENDIX A BLOWER PERFORMANCE TABLES
BELT DRIVE
HIGH STATIC DOWN SHOT
CPC036 HIGH STATIC BELT DRIVE DOWN SHOT
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.6
1692
0.54
1449
0.41
1173
0.29
0.8
1678
0.58
1397
0.44
1107
0.31
854
0.21
1.0
1681
0.65
1381
0.49
1078
0.34
794
0.22
1.2
1681
0.71
1362
0.54
1062
0.39
1.4
1362
0.60
1066
0.44
1.6
1066
0.50
789
0.34
1.8
789
0.40
CPC048 HIGH STATIC BELT DRIVE DOWN SHOT
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.6
2194
0.85
1886
0.66
1580
0.49
0.8
2113
0.86
1832
0.70
1526
0.52
1219
0.37
1.0
2182
0.98
1776
0.73
1472
0.55
1166
0.39
1.2
2053
1.00
1780
0.80
1440
0.59
1111
0.40
1.4
1759
0.86
1421
0.64
1104
0.46
1.6
1442
0.72
1095
0.50
1.8
1095
0.56
CPC/H060 HIGH STATIC BELT DRIVE DOWN SHOT
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.6
2331
1.01
2072
0.80
0.8
2324
1.10
2059
0.87
1791
0.66
1.0
2350
1.21
2058
0.95
1774
0.72
1.2
2367
1.33
2086
1.06
1776
0.79
1.4
2404
1.45
2111
1.17
1805
0.89
1.6
2136
1.28
1835
0.99
1.8
1868
1.10
CPC/H072 HIGH STATIC BELT DRIVE DOWN SHOT
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.6
2793
1.64
2603
1.39
2450
1.182
2270
0.97
0.8
2903
1.87
2696
1.57
2369
1.23
2236
1.05
1987
0.82
1.0
2776
1.86
2683
1.69
2445
1.38
2196
1.12
1968
0.90
1.2
2599
1.71
2539
1.57
2310
1.29
1932
0.96
1.4
2424
1.57
2305
1.40
2032
1.11
1.6
2172
1.38
2017
1.19
1.8
1953
1.22
NOTES:
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5
Tables represent dry coil without filter, to co mpensate for filter add 0.08" to measured E.S.P.
SCFM correction for wet coil = 4 %.