Pre-installation checks, Flue, Additional ventilation – Stovax Riva Plus Midi Wood & Multi-fuel User Manual
Page 17

17
PRe-INsTAllATIoN CHeCKs
1. FlUe
Model
:
Riva Plus Small RVP-SMM/RVP-SMW
Riva Plus Large RVP-LAM/RVP-LAW
Riva
Traditional
small
RVP-SMM/RVP-SMW
Riva
Traditional
large
RVP-LAM/RVP-LAW
Flue/Chimney Size
Without flue liner Round (diameter)
mm
150
150
inch
6
6
Without flue liner system Square
(diameter)
mm
135
135
inch
5
1
/
2
5
1
/
2
With liner or Factory made system
(diameter)
installed in accordance with manufacturer's instructions
mm
†150
†150
inch
†6
†6
Flue/Chimney
(*minimum height)
All products
metre
4.5
4.5
feet
13
13
* When measured from the top of the stove to the top of the flue, with no
horizontal sections and a maximum of 4 bends with angles of less than 45o
†May be 125mm (5") if only burning low volatiles (smokeless) fuels approved for use in Smoke Control Areas.
See website http://uksmokecontrolareas.co.uk for more information about approved fueld
2.1 Additional ventilation is required to comply with the
requirements of the Building Regulations. This must be
provided using a permanently open air vent, of the size
listed, which is positioned so that it is not liable to be
blocked both inside and outside the building.
2.2 Extractor fans or cooker hoods must not be placed in the
same room or space as this can cause the appliance to emit
fumes into the room.
2.3 If any of these checks reveal problems do not proceed
with the fitting of the appliance until they have been
rectified.
2. AddITIoNAl VeNTIlATIoN
Model
:
Riva Plus Small RVP-SMM/RVP-SMW
Riva Plus Large RVP-LAM/RVP-LAW
Riva
Traditional
small
RVP-SMM/RVP-SMW
Riva
Traditional
large
RVP-LAM/RVP-LAW
Additional Ventilation
mm
2
NONE
3300
cm
2
NONE
33.0
in
2
NONE
5.12