BLOWER PERFORMANCE SPECIFICATIONS

12

1.

CFM in chart is without filters(s). Filters do not ship with this furnace, but must be provided by the installer.

2.

All furnaces ship as high speed cooling. Installer must adjust blower cooling speed as needed.

3.

For most jobs, about 400 CFM per ton when cooling is desirable.

4.

INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.

5.

The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate. The shaded
area indicates ranges in excess of maximum external static pressure allowed when heating. The data for 0.6" w.c. to 0.8" w.c. is shown for
air conditioning purposes only.

6

The dashed (---) areas indicate a temperature rise not recommended for this model.

7.

The above chart is for U.S. furnaces installed at 0-4000 feet. At higher altitudes, a properly derated unit will have approximately the same
temperature rise at a particular CFM, while the ESP at that CFM will be lower.

Tons AC

at 0.5"

0.6

0.7

0.8

ESP

CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM

T1

2.5

875

59

793

65

736

70

674

77

592

88

556

509

460

T2

3.5

1,032

50

965

54

914

57

861

60

810

64

756

712

659

T3

1.5

1,217

43

1,153

45

1,098

47

1,051

49

1,009

51

964

918

877

T4

3

1,365

38

1,313

39

1,268

41

1,221

42

1,172

44

1,129 1,086 1,054

T5

4

1,549

33

1,505

34

1,460

36

1,420

37

1,378

38

1,350 1,305 1,268

T1

2.5

1,268

53

1,198

56

1,151

58

1,092

61

1,041

64

988

932

883

T2

3.5

1,362

49

1,305

51

1,261

53

1,212

55

1,170

57

1,121 1,074 1,021

T3

3

1,576

42

1,519

44

1,473

45

1,426

47

1,398

48

1,341 1,290 1,252

T4

4

1,755

38

1,711

39

1,657

40

1,627

41

1,579

42

1,548 1,502 1,463

T5

5

2,183

31

2,128

31

2,094

32

2,060

32

2,014

33

1,992 1,944 1,847

T1

3

1,466

58

1,415

60

1,357

63

1,306

65

1,248

68

1,202 1,144 1,088

T2

4

1,642

52

1,596

53

1,552

55

1,499

57

1,449

59

1,388 1,352 1,306

T3

2.5

1,750

49

1,750

49

1,707

50

1,667

51

1,610

53

1,574 1,531 1,486

T4

4

1,870

46

1,805

47

1,782

48

1,737

49

1,701

50

1,656 1,606 1,571

T5

5

2,297

37

2,297

37

2,224

38

2,106

40

2,014

42

1,896 1,813 1,669

BLOWER PERFORMANCE

0.1

0.2

0.3

0.4

0.5

(CFM & Temperature Rise vs. External Static Pressure)

Model

Heating Speed

As Shipped

EXTERNAL STATIC PRESSURE (Inches Water Column)

GME8

1155CXC*

GME8

0905CXC*

GME8

0703BXC*

Motor

Speed

(

)