Vaporator, Lower, Pecifications – Goodman Mfg PC50 User Manual
Page 5

P
RODUCT
S
PECIFICATIONS
SS-PC50
www.goodmanmfg.com
5
E
VAPORATOR
B
LOWER
S
PECIFICATIONS
Model
Speed
Airfl ow
External Static Pressure In-Water [Mbar]
0.1 [0.25]
0.2 [0.5]
0.3 [0.75]
0.4 [1.0]
0.5 [1.25]
PC060-5A
Low
CFM [L/s]
1885 [890]
1840 [870]
1795 [850]
1675 [790]
1575 [740]
High
CFM [L/s]
2030 [960]
1955 [920]
1900 [900]
1760 [830]
1655 [780]
PC048-5A
Low
CFM [L/s]
1540 [730]
1450 [680]
1315 [620]
1215 [570]
1070 [500]
High
CFM [L/s]
1590 [750]
1490 [700]
1395 [660]
1280 [600]
1120 [530]
[ ] Designates metric measurements
Notes:
1. Data shown is dry coil. Wet coil pressure drop is approx.
2. 0.1” H2O, for two-row indoor coil; 0.2” H
2
O, for three-row indoor coil; and 0.3” H
2
O, for four-row indoor coil.
3. Data shown does not include fi lter pressure drop, approx. 0.08” H
2
O.
4. ALL MODELS SHOULD RUN NO LESS THAN 350 CFM/TON. USE HIGHER SPEED TAP OR NEXT SIZE LARGER BLOWER
ASM., See Repair Parts list.
5. Reduce airfl ow by 2% for 208-volt operation.