Xpanded, Ooling, Atings – Goodman Mfg PC50 User Manual
Page 4: Pc048-5g, Pc060-5g, Roduct, Pecifications
![background image](/manuals/111816/4/background.png)
P
RODUCT
S
PECIFICATIONS
4 www.goodmanmfg.com
SS-PC50
E
XPANDED
C
OOLING
R
ATINGS
PC048-5G
Indoor
Air
Condenser Air Temperature
75
85
95
105
115
SCFM
WB
Total
MBTU
Sens
MBTU
Watts
kWh
Total
MBTU
Sens
MBTU
Watts
kWh
Total
MBTU
Sens
MBTU
Watts
kWh
Total
MBTU
Sens
MBTU
Watts
kWh
Total
MBTU
Sens
MBTU
Watts
kWh
1194
71
48.1
23.5
4.05
46.9
23.6
4.32
45.8
23.7
4.56
43.5
23.4
4.76
40.3
21.8
4.93
67
45.0
29.5
3.92
43.9
29.5
4.18
42.8
29.7
4.41
40.7
29.3
4.60
37.7
27.3
4.77
63
42.1
33.9
3.80
41.1
33.9
4.04
40.1
34.1
4.26
38.1
33.7
4.45
35.3
31.4
4.61
59
41.2
35.3
3.71
40.2
35.4
3.96
39.2
35.6
4.17
37.3
35.1
4.35
34.5
32.8
4.50
1365
71
52.1
26.4
4.16
50.8
26.5
4.44
49.6
26.7
4.68
47.1
26.3
4.89
43.6
24.6
5.06
67
48.7
33.1
4.02
47.6
33.1
4.29
46.4
33.4
4.52
44.1
32.9
4.72
40.8
30.7
4.89
63
45.6
38.1
3.90
44.5
38.1
4.15
43.4
38.4
4.37
41.3
37.8
4.57
38.2
35.3
4.73
59
44.6
39.7
3.81
43.6
39.8
4.06
42.5
40.0
4.28
40.4
39.5
4.46
37.4
36.9
4.62
1536
71
53.6
28.6
4.20
52.4
28.6
4.47
51.1
28.8
4.72
48.5
28.4
4.93
45.0
26.5
5.11
67
50.2
35.7
4.06
49.0
35.8
4.33
47.8
36.0
4.56
45.4
35.5
4.76
42.1
33.2
4.94
63
47.0
41.1
3.93
45.9
41.1
4.19
44.7
41.4
4.41
42.5
40.9
4.61
39.4
38.2
4.77
59
46.0
42.9
3.84
44.9
42.9
4.09
43.8
43.8
4.31
41.6
41.6
4.50
38.5
38.5
4.66
Sensible heat capacities shown are based on 80°F DB entering air at the evaporator coil.
For sensible heat capacities at other than 80°F DB, deduct 84 BTU/h per 100 CFM of evaporator coil air for each degree
below 80°F, or add 84 BTU/h per 100 CFM of evaporator coil air per degree above 80°F.
Total MBTU/h
43.0
Sensible MBTU/h
33.0
Latent MBTU/h
10.0
PC060-5G
Indoor
Air
Condenser Air Temperature
75
85
95
105
115
SCFM
WB
Total
MBTU
Sens
MBTU
Watts
kWh
Total
MBTU
Sens
MBTU
Watts
kWh
Total
MBTU
Sens
MBTU
Watts
kWh
Total
MBTU
Sens
MBTU
Watts
kWh
Total
MBTU
Sens
MBTU
Watts
kWh
1481
71
56.7
27.7
5.23
55.3
27.8
5.57
54.0
28.0
5.87
51.3
27.6
6.12
47.5
25.8
6.35
67
53.0
34.7
5.06
51.8
34.8
5.39
50.5
35.0
5.68
48.0
34.5
5.92
44.4
32.2
6.13
63
49.6
39.9
4.90
48.4
40.0
5.21
47.3
40.3
5.49
44.9
39.7
5.73
41.6
37.1
5.93
59
48.6
41.7
4.79
47.4
41.7
5.10
46.2
42.0
5.37
43.9
41.4
5.60
40.7
38.7
5.80
1693
71
61.4
31.2
5.36
59.9
31.2
5.71
58.5
31.4
6.02
55.6
31.0
6.29
51.5
28.9
6.52
67
57.4
39.0
5.19
56.1
39.1
5.53
54.7
39.3
5.83
52.0
38.8
6.08
48.1
36.2
6.30
63
53.8
44.9
5.02
52.5
44.9
5.35
51.2
45.2
5.64
48.6
44.6
5.88
45.1
41.7
6.09
59
52.6
46.8
4.92
51.4
46.9
5.23
50.1
47.2
5.51
47.6
46.5
5.75
44.1
43.5
5.95
1905
71
63.2
33.7
5.41
61.7
33.7
5.76
60.2
33.9
6.08
57.2
33.5
6.34
53.0
31.3
6.57
67
59.2
42.1
5.23
57.7
42.2
5.57
56.3
42.5
5.87
53.5
41.9
6.13
49.6
39.1
6.35
63
55.4
48.5
5.07
54.1
48.5
5.39
52.7
48.8
5.68
50.1
48.2
5.93
46.4
45.0
6.14
59
54.2
50.6
4.96
52.9
50.6
5.28
51.6
51.6
5.56
49.0
49.0
5.80
45.4
45.4
6.01
Sensible heat capacities shown are based on 80°F DB entering air at the evaporator coil.
For sensible heat capacities at other than 80°F DB, deduct 84 BTU/h per 100 CFM of evaporator coil air for each degree
below 80°F, or add 84 BTU/h per 100 CFM of evaporator coil air per degree above 80°F.
Total MBTU/h
50.7
Sensible MBTU/h
38.9
Latent MBTU/h
11.8