beautypg.com

Xpanded, Ooling, Atings – Goodman Mfg PC50 User Manual

Page 4: Pc048-5g, Pc060-5g, Roduct, Pecifications

background image

P

RODUCT

S

PECIFICATIONS

4 www.goodmanmfg.com

SS-PC50

E

XPANDED

C

OOLING

R

ATINGS

PC048-5G

Indoor

Air

Condenser Air Temperature

75

85

95

105

115

SCFM

WB

Total

MBTU

Sens

MBTU

Watts

kWh

Total

MBTU

Sens

MBTU

Watts

kWh

Total

MBTU

Sens

MBTU

Watts

kWh

Total

MBTU

Sens

MBTU

Watts

kWh

Total

MBTU

Sens

MBTU

Watts

kWh

1194

71

48.1

23.5

4.05

46.9

23.6

4.32

45.8

23.7

4.56

43.5

23.4

4.76

40.3

21.8

4.93

67

45.0

29.5

3.92

43.9

29.5

4.18

42.8

29.7

4.41

40.7

29.3

4.60

37.7

27.3

4.77

63

42.1

33.9

3.80

41.1

33.9

4.04

40.1

34.1

4.26

38.1

33.7

4.45

35.3

31.4

4.61

59

41.2

35.3

3.71

40.2

35.4

3.96

39.2

35.6

4.17

37.3

35.1

4.35

34.5

32.8

4.50

1365

71

52.1

26.4

4.16

50.8

26.5

4.44

49.6

26.7

4.68

47.1

26.3

4.89

43.6

24.6

5.06

67

48.7

33.1

4.02

47.6

33.1

4.29

46.4

33.4

4.52

44.1

32.9

4.72

40.8

30.7

4.89

63

45.6

38.1

3.90

44.5

38.1

4.15

43.4

38.4

4.37

41.3

37.8

4.57

38.2

35.3

4.73

59

44.6

39.7

3.81

43.6

39.8

4.06

42.5

40.0

4.28

40.4

39.5

4.46

37.4

36.9

4.62

1536

71

53.6

28.6

4.20

52.4

28.6

4.47

51.1

28.8

4.72

48.5

28.4

4.93

45.0

26.5

5.11

67

50.2

35.7

4.06

49.0

35.8

4.33

47.8

36.0

4.56

45.4

35.5

4.76

42.1

33.2

4.94

63

47.0

41.1

3.93

45.9

41.1

4.19

44.7

41.4

4.41

42.5

40.9

4.61

39.4

38.2

4.77

59

46.0

42.9

3.84

44.9

42.9

4.09

43.8

43.8

4.31

41.6

41.6

4.50

38.5

38.5

4.66

Sensible heat capacities shown are based on 80°F DB entering air at the evaporator coil.
For sensible heat capacities at other than 80°F DB, deduct 84 BTU/h per 100 CFM of evaporator coil air for each degree
below 80°F, or add 84 BTU/h per 100 CFM of evaporator coil air per degree above 80°F.
Total MBTU/h

43.0

Sensible MBTU/h

33.0

Latent MBTU/h

10.0

PC060-5G

Indoor

Air

Condenser Air Temperature

75

85

95

105

115

SCFM

WB

Total

MBTU

Sens

MBTU

Watts

kWh

Total

MBTU

Sens

MBTU

Watts

kWh

Total

MBTU

Sens

MBTU

Watts

kWh

Total

MBTU

Sens

MBTU

Watts

kWh

Total

MBTU

Sens

MBTU

Watts

kWh

1481

71

56.7

27.7

5.23

55.3

27.8

5.57

54.0

28.0

5.87

51.3

27.6

6.12

47.5

25.8

6.35

67

53.0

34.7

5.06

51.8

34.8

5.39

50.5

35.0

5.68

48.0

34.5

5.92

44.4

32.2

6.13

63

49.6

39.9

4.90

48.4

40.0

5.21

47.3

40.3

5.49

44.9

39.7

5.73

41.6

37.1

5.93

59

48.6

41.7

4.79

47.4

41.7

5.10

46.2

42.0

5.37

43.9

41.4

5.60

40.7

38.7

5.80

1693

71

61.4

31.2

5.36

59.9

31.2

5.71

58.5

31.4

6.02

55.6

31.0

6.29

51.5

28.9

6.52

67

57.4

39.0

5.19

56.1

39.1

5.53

54.7

39.3

5.83

52.0

38.8

6.08

48.1

36.2

6.30

63

53.8

44.9

5.02

52.5

44.9

5.35

51.2

45.2

5.64

48.6

44.6

5.88

45.1

41.7

6.09

59

52.6

46.8

4.92

51.4

46.9

5.23

50.1

47.2

5.51

47.6

46.5

5.75

44.1

43.5

5.95

1905

71

63.2

33.7

5.41

61.7

33.7

5.76

60.2

33.9

6.08

57.2

33.5

6.34

53.0

31.3

6.57

67

59.2

42.1

5.23

57.7

42.2

5.57

56.3

42.5

5.87

53.5

41.9

6.13

49.6

39.1

6.35

63

55.4

48.5

5.07

54.1

48.5

5.39

52.7

48.8

5.68

50.1

48.2

5.93

46.4

45.0

6.14

59

54.2

50.6

4.96

52.9

50.6

5.28

51.6

51.6

5.56

49.0

49.0

5.80

45.4

45.4

6.01

Sensible heat capacities shown are based on 80°F DB entering air at the evaporator coil.
For sensible heat capacities at other than 80°F DB, deduct 84 BTU/h per 100 CFM of evaporator coil air for each degree
below 80°F, or add 84 BTU/h per 100 CFM of evaporator coil air per degree above 80°F.
Total MBTU/h

50.7

Sensible MBTU/h

38.9

Latent MBTU/h

11.8