beautypg.com

High wind and hurricane zone fans, Clean air roof exhaust fan – Greenheck Fan H-GB User Manual

Page 8

background image

P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com

Promo High Wind & Hurricane Fans

Rev. 4 November 2008

Copyright © 2008 Greenheck

Prepared to Support

Green Building Efforts

The Greenheck models LBP / LDP are louvered penthouse
powered roof exhaust fans. The LBP / LDP are designed

specifically for general clean air exhaust on life safety and
critical facilities. The backward inclined centrifugal wheel is

enclosed in the SDLE (severe duty louvered enclosure) which
is constructed completely of Miami-Dade Approved louvers
model ESD-603 and passes all Miami-Dade and Florida

Building Code requirements (TAS-201/202/203). The louvered

enclosure is designed to meet all static, cyclic and missile impact requirements for high
wind and hurricane zones. The structural steel interior, extruded aluminum blades and high
strength frame provide the added strength required to withstand design pressures of up to
140 psf. It ships mounted to a standard 24 inch tall SD (Severe Duty) 12 gauge steel curb
and tie downs to the roof are not required.

Performance:

For full performance listings refer to the

LBP / LDP catalog
• Air performance is AMCA certified from 100-14,200 cfm
• Pressure range from 0-1.25 inches wg
• Units are licensed to bear the AMCA seal for sound and air

Certifications:

Third party certifications

• Miami-Dade County Approval NOA# 03-0422.05
• Florida Product Approval No: FL4825.1

Standard Construction

Exterior:

High strength ESD-603 Miami-Dade louvers

Internal Bracing:

Integral high strength internal bracing structure

Wheel Assembly:

Backward inclined wheel is closely matched to the inlet

venturi for precise running tolerances and consistent performance

Drive Assembly:

Motor and drive frame are connected directly to the internal

frame, mounted on true vibration isolators and sized for 150% of maximum
driven horsepower

Bearings:

Bearings are pillow block design selected for a minimum average

L50 life in excess of 500,000 hours (basic L10 life of 100,000 hours) at
maximum cataloged speed

Disconnect:

NEMA-1 disconnect is mounted and wired from the factory

High Wind and Hurricane Zone Fans

Clean Air Roof Exhaust Fan

This manual is related to the following products: