Pressure drop data fsd-311v, Amca test figures, D4 (w) (h) 3.14 – Greenheck Fan Steel Airfoil Blades FSD-311V User Manual

Page 2

background image

Pressure drop data

Fsd-311V

This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All

data has been corrected to represent standard air at a density of .075 lb/ft

3

(1.2 kg/m

3

).

Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an

analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC

system.

AmCA Test Figures

Figure 5.3 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test configurations

because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper.

Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop than Fig-

ure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.

Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely high

entrance and exit losses due to the sudden changes of area in the system.