MI00/10056 rev. 8 —05/2006
A.C. Supply
Reserve Supply
UPS Type
V
in
/V
out
Rated
current (A)
Protection
device (A)
Output
Nominal
current (A)
Nominal
current (A)
Protection
device (A)
24/12kVA
42
60
33
33
50
24/18kVA
60
80
50
50
70
24/24kVA
208/120-
208/120
78
100
67
67
90
24/12kVA
19
30
33
14
20
24/18kVA
26
40
50
22
30
24/24kVA
480-208/120
34
50
67
29
40
24/12kVA
19
30
14
14
20
24/18kVA
26
40
22
22
30
24/24kVA
480-480/277
34
50
29
29
40
36/24kVA
78
125
67
67
90
36/30kVA
97
150
83
83
125
36/36kVA
208/120-
208/120
118
160
100
100
150
36/24kVA
34
50
67
29
40
36/30kVA
42
60
83
36
50
36/36kVA
480-208/120
51
70
100
43
60
36/24kVA
34
50
29
29
40
36/30kVA
42
60
36
36
50
36/36kVA
480/277-
480/277
51
70
43
43
60
50/30kVA
132
175
83
83
125
50/40kVA
152
200
111
111
150
50/50kVA
208-208/120
192
250
138
138
175
50/30kVA
57
80
83
36
50
50/40kVA
66
90
111
48
60
50/50kVA
480-208/120
83
125
138
60
80
50/30kVA
57
80
36
36
50
50/40kVA
66
90
48
48
60
50/50kVA
480-480/277
83
125
60
60
80
80/50kVA
192
250
139
139
175
80/65kVA
254
350
180
180
225
80/80kVA
208-208/120
311
400
222
222
300
80/50kVA
83
125
139
60
80
80/65kVA
110
150
180
78
100
80/80kVA
480-208/120
135
175
222
96
125
80/50kVA
83
125
60
60
80
80/65kVA
110
150
78
78
100
80/80kVA
480-480/277
135
175
96
96
125