beautypg.com

Gmvm96 a, Irflow, Ooling – Goodman Mfg VARIABLE-SPEED GAS FURNACE GMVM96 User Manual

Page 6: Peeds

background image

6

www.goodmanmfg.com

SS-GMVM96

SS-GMVM96

www.goodmanmfg.com

7

P

roduct

S

PecificationS

P

roduct

S

PecificationS

GMVM96 a

irflow

d

ata

— C

ooliNG

s

peeds

GMVM960603BX

GVMV960805CX

High Stage

Low Stage

High Stage

Low Stage

Tap

Adjust

CFM*

Tap

Adjust

CFM*

Tap

Adjust

CFM*

Tap

Adjust

CFM*

A

Minus(-)

567

A

Minus(-)

351

A

Minus(-)

747

A

Minus(-)

486

Normal

630

Normal

390

Normal

830

Normal

540

Plus (+)

693

Plus (+)

429

Plus (+)

913

Plus (+)

594

B

Minus(-)

720

B

Minus(-)

495

B

Minus(-)

981

B

Minus(-)

675

Normal

800

Normal

550

Normal

1090

Normal

750

Plus (+)

880

Plus (+)

605

Plus (+)

1199

Plus (+)

825

C

Minus(-)

900

C

Minus(-)

612

C

Minus(-)

1314

C

Minus(-)

882

Normal

1000

Normal

680

Normal

1460

Normal

980

Plus (+)

1100

Plus (+)

748

Plus (+)

1606

Plus (+)

1078

D

Minus(-)

1089

D

Minus(-)

720

D

Minus(-)

1620

D

Minus(-)

1089

Normal

1210

Normal

800

Normal

1800

Normal

1210

Plus (+)

1331

Plus (+)

880

Plus (+)

1980

Plus (+)

1331

* @ .1" - .8" w.c. ESP

* @ .1" - .8" w.c. ESP

GMVM961005DX

GMVM961155DX

High Stage

Low Stage

High Stage

Low Stage

Tap

Adjust

CFM*

Tap

Adjust

CFM*

Tap

Adjust

CFM*

Tap

Adjust

CFM*

A

Minus(-)

711

A

Minus(-)

459

A

Minus(-)

711

A

Minus(-)

459

Normal

790

Normal

510

Normal

790

Normal

510

Plus (+)

869

Plus (+)

561

Plus (+)

869

Plus (+)

561

B

Minus(-)

990

B

Minus(-)

639

B

Minus(-)

990

B

Minus(-)

639

Normal

1100

Normal

710

Normal

1100

Normal

710

Plus (+)

1210

Plus (+)

781

Plus (+)

1210

Plus (+)

781

C

Minus(-)

1269

C

Minus(-)

819

C

Minus(-)

1269

C

Minus(-)

819

Normal

1410

Normal

910

Normal

1410

Normal

910

Plus (+)

1551

Plus (+)

1001

Plus (+)

1551

Plus (+)

1001

D

Minus(-)

1647

D

Minus(-)

1044

D

Minus(-)

1647

D

Minus(-)

1044

Normal

1830

Normal

1160

Normal

1830

Normal

1160

Plus (+)

2013

Plus (+)

1276

Plus (+)

2013

Plus (+)

1276

* @ .1" - .8" w.c. ESP

Notes:

• All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
• For most jobs, about 400 CFM per ton when cooling is desirable.
• Operation is recommended below .5” w.c. ESP in heating mode. Operating CFM between .5” and .8” w.c. is tabulated for cooling purposes only.