BLOWER PERFORMANCE DATA

8

C ------- 7.5 min/82% 60 sec/100%

Profiles Pre-Run Short-Run OFF Delay

To set Comfort Mode:

B ------- 30 sec/50% 60 sec/100%

Speed Selection Dip Switches

0140A00048 REV A

A OFF OFF OFF OFF OFF OFF

D 30 sec/50% 7.5 min/82% 30 sec/50%

To set airflow:

TAP 1 2 3 4 5 6

B ON OFF ON OFF ON OFF

A ------- -------- 60 sec/100%

Select desired Comfort Mode profile

(see profiles above). Set switches 5 and 6 to the approriate
ON / OFF positions.

(1) Select model and desired

high stage cooling airflow. Determine the cooresponding tap

( A, B, C, or D ). Set dip switches 1 and 2 to the appropriate

ON / OFF positions. (2) Select model and installed electric
heater size. Set switches 9, 10, and 11 to the appropriate

ON/OFF positions. (3) Select the airflow adjustment factor tap
A and D are 0%; Tap B is +10%; Tap C -10%. Set dip switches 3

and 4 to the appropriate ON / OFF positions.

C OFF ON OFF ON OFF ON

D ON ON ON ON ON ON

Cool Adjust Profile

Selection Selection Selection

Switches Switches Switches

20 OFF OFF ON NR NR 1600

15 OFF ON OFF NR 1400 1400

10 OFF ON ON 1200

1200 1200

8 ON OFF OFF 1000 1000 1000

6 ON OFF ON 800 800 800

5 ON ON OFF 700

700

700

3 ON ON ON 600 600 600

Htr Kw 9 10 11 AVPTC 183014*

AVPTC 313714* AVPTC 426014

*

21 OFF OFF OFF NR NR 1600

C ------- 7.5 min/82% 60 sec/100%

C ------- 7.5 min/82% 60 sec/100%

C ------- 7.5 min/82% 60 sec/100%

B ------- 30 sec/50% 60 sec/100%

B ------- 30 sec/50% 60 sec/100%

B ------- 30 sec/50% 60 sec/100%

D 30 sec/50% 7.5 min/82% 30 sec/50%

D 30 sec/50% 7.5 min/82% 30 sec/50%

D 30 sec/50% 7.5 min/82% 30 sec/50%

D 30 sec/50% 7.5 min/82% 30 sec/50%

To set airflow:

(1) Select model and desired

To set airflow:

(1) Select model and desired

(1) Select model and desired

high stage cooling airflow. Determine the cooresponding tap

high stage cooling airflow. Determine the cooresponding tap

( A, B, C, or D ). Set dip switches 1 and 2 to the appropriate

ON / OFF positions. (2) Select model and installed electric

A 810 1210

C 1047 1562

D 1209 1804

A 409 610

B 553 825
C 696 1040
D 829 1237

A 422 630
B 563 840
C 694 1036
D 825 1232

AVPTC 183014

*

Model Tap Low Stage High Stage
Cool Cool

AVPTC 313714

*

AVPTC 426014

*

A 409 610

A 409 610

A 409 610

B 553 825

B 553 825

B 553 825
C 696 1040

C 696 1040

C 696 1040

A 422 630

A 422 630

A 422 630
B 563 840

B 563 840

B 563 840
C 694 1036

C 694 1036

C 694 1036
D 825 1232

D 825 1232

D 825 1232

AVPTC 183014

*

AVPTC 313714

*

Electric Heat Airflow and Temperature Rise Table

Cooling/Heat Pump Airflow Table

NOTE: Airflow data shown applies to the emergency heat mode (electric heat only)
in either legacy mode operation or fully communicating mode operation.

MODELS

AVPTC183014A*

AVPTC313714*

AVPTC426014A*

HKR-03*

X

X

X

HKR-05*/-05C*

X

X

X

HKR-06*

X

X

X

HKR-08*/-08C*

X

X

X

HKR-10*/-10C*

X

1

X

X

HKR-15C

X

2

X

HKR-20C

X

3

HKR-21C

X

3

Heat Kit Selection

*

Revision level that may or may not be designated.

C

Circuit breaker option.

1

For units operating in Legacy mode, use dip switches 9-ON, 10-OFF, 11-OFF, to obtain 1000 CFM, or 9-OFF, 10-ON, 11-ON to obtain 1200 CFM.

For units operating in Communicating mode, use dip switch 8 kW Htr to obtain 1000 CFM or 10 kW Htr to obtain 1200 CFM.

2

This heater kit can only be used for ‘1000 CFM or higher’ applications.

3

This heater kit can only be used for ‘1200 CFM or higher’ applications.