Actuators and Accessories

space envelopes

Externally mounted actuators always require space outside

of the damper sleeve. The “S” dimension illustrates the

clearance required for various available actuators.

On dampers less than 18 in. (457mm) high, actuators

may also require clearances above and/or below the

sleeve. “B” and “T” dimensions are worst case clearance

requirements for some dampers less than 18 in. (457mm)

high. All damper sizes under 18 in. (457mm) high do not

require these worst case clearances. If space availability

above or below the damper sleeve is limited, each damper

size should be individually evaluated.

damper sleeve dimensional data

The drawings below and corresponding table show the position of the FSD-211 damper when mounted in a factory sleeve.

The standard mounting locations provide enough space for the mounting of actuators, controls and allow space for

installation of retaining angles and duct connections.

The standard location of a damper mounted in a factory sleeve ("A" dimension) is shown below. The damper can be

positioned at other locations within a range of 6 in. (152mm) to 12 in. (305mm) for the "A" dimension.

Application data

5

3

/

8

in.

5 in.

Right hand drive is show n

Left hand drive available upon re quest

LH

RH

A

Sleeve Length

V aries

6 in.

3

3

/

4

1

1

/

2

in.

max.

B*

S

T*

in.

*With the exception of dampers 10 in. high (254mm) or less.

NOTE: Entire damper frame is not required to be installed within the

wall. The damper blades, when closed should be contained within

the wall.

in. (mm)

"A" Dimension

Standard

Maximum

All Dampers*

7 3/16 (183)

12 (305)

When H is 11 in. (279mm) or
less with OCI, RRL, or TOR

12 (305)

12 (305)

* For dampers 18 in. (457mm) or more in height these dimensions are 0 in. .

Actuator Type/Model

B*

T*

S

With

RRL, RRL/OCI, or TOR

With

RRL, RRL/OCI, or TOR

120 Volt AC

ML-4XXX Series Honeywell

5¼ in. (133mm)

¾ in.(19mm)

6 in. (152mm)

MS-4XXX Series Honeywell

6 in. (152mm)

3/8 in. (10mm)

6 in. (152mm)

MS-4120 Series Honeywell

6 in. (152mm)

3/8 in. (10mm)

6 in. (152mm)

24 Volt AC

ML-8XXX Series Honeywell

5¼ in. (133mm)

¾ in.(19mm)

6 in. (152mm)

MS-8XXX Series Honeywell

6 in. (152mm)

6 in. (152mm)

6 in. (152mm)

MS-8120 Series Honeywell

6 in. (152mm)

6 in. (152mm)

6 in. (152mm)

Pneumatic (25 psi min.)

331-4551 Powers

1 in. (25mm)

6¼ in. (159mm)

6½ in. (165mm)

331-2976 Powers

2 3/8 in. (60mm)

12 1/8 in. (308mm)

9¼ in. (235mm)

MK2-7121 Invensys

3 3/4 in. (95mm)

16½ in. (419mm)

10 in. (254mm)