beautypg.com

Module selection options, None – Greenheck Fan Modular Make-Up Air Unit DGX User Manual

Page 3

background image

3

MODULE SELECTION OPTIONS

Module 1

INTAKE

Module 2

FILTER

Module 3

COOLING

Module 4

HEATING

Module 5

DISCHARGE

Option 1

None

requires

Module 2, Option 2

None

None

Direct Gas Furnace

100% Outdoor Air

Downblast

Discharge

Option 2

Birdscreen Weatherhood

requires

Module 2, Option 2

V-Bank Filters

Pleated or

Aluminum Mesh

*Cooling Coil – CW, DX

(standard capacity)

Direct Gas Furnace

Recirculation - requires

Module 2, Option 3

Horizontal
Discharge

Option 3

Filtered

Weatherhood

80/20 Filtered

Recirculation

*Cooling Coil – CW, DX

(high capacity)

Direct Gas Furnace

Variable Air Volume

Upblast

Discharge

Option 4

Louvered

Weatherhood

Option 5

Thru-Wall

Option 6

Evaporative

Cooling

*Chilled water or direct expansion (DX) cooling is available with the model DGX. The cooling section

includes the cooling coil, sloped stainless steel drain pan and insulated double wall construction.
Drain and coil connections are stubbed through the wall for convenience.

For proper coil sizing, use Greenheck CAPS selection software or contact your local representative.

Four row and six row chilled water or DX coils are available with airflow capacity up to 11,000 cfm.

Cooling coil sections are installed upstream of the fan section for a draw through arrangement and

provide a streamlined transition to adjacent DGX sections. DX coils require remote condensing units.

• Module 2 is not available with the Evaporative Cooler section (Module 1, Option 6)
• Cooling Coil modules (Module 3, Option 2 & 3) are not available with Recirculation (Module 2,

Option 3)

• Optional intake dampers available on Cooling Coil section (Module 3, Option 2 & 3)
• Module 1, Option 3, 4 & 5 are not available on Housing 35 and larger

The evaporative cooling section includes a galvanized steel housing with a louvered intake, 2 inch
aluminum mesh filters and a stainless steel evaporative cooling module. The evaporative cooling
media has a depth of 12 inches for 90% cooling effectiveness.
The entire section mounts directly to the front of the DGX unit, eliminating transition or ductwork
by others. Drain and overflow are conveniently tapped through the side of the cooling section. The
supply line connection is field located where convenient. Freeze protection, automatic drain & fill, and
water economizer (Water Wizard) options are also available.
Airflow capacity for evaporative cooling is up to 46,000 cfm. The evaporative cooling section for the
housing 32 and larger ship separately.