beautypg.com

Installation instructions, Thermal expansion, Location (cont.) – GE GEH50DXSRGA User Manual

Page 15

background image

Installation Instructions

THERMAL EXPANSION

Determine if a check valve exists in the inlet water

line. It may have been installed in the cold water line as

a separate backflow preventer, or it may be part of a

pressure-reducing valve, water meter or water softener.

A check valve located in the cold water inlet line can

cause what is referred to as a “closed water system.”

A cold water inlet line with no check valve or backflow

prevention device is referred to as an “open” water

system.
As water is heated, it expands in volume and creates

an increase in the pressure within the water system.

This action is referred to as “thermal expansion.” In an

“open” water system, expanding water which exceeds the

capacity of the water heater flows back into the city main

where the pressure is easily dissipated.
A “closed water system,” however, prevents the

expanding water from flowing back into the main

supply line, and the result of “thermal expansion” can

create a rapid and dangerous pressure increase in the

water heater and system piping. This rapid pressure

increase can quickly reach the safety setting of the relief

valve, causing it to operate during each heating cycle.

Thermal expansion, and the resulting rapid and repeated

expansion and contraction of components in the water

heater and piping system, can cause premature failure of

the relief valve, and possibly the heater itself. Replacing

the relief valve will not correct the problem!
The suggested method of controlling thermal expansion

is to install an expansion tank in the cold water line

between the water heater and the check valve (refer to

the illustration on right). The expansion tank is designed

with an air cushion built in that compresses as the system

pressure increases, thereby relieving the over-pressure

condition and eliminating the repeated operation of

the relief valve. Other methods of controlling thermal

expansion are also available. Contact your installing

contractor, water supplier or plumbing inspector for

additional information regarding this subject.

15

LOCATION (CONT.)

A— Diameter of water heater

plus 2” (5.1 cm) min.

B— Maximum 2” (5.1 cm)

NOTE: Auxiliary catch pan MuST conform to local codes.
Catch Pan Kits are available from the store where the water

heater was purchased, a builder store or any water heater

distributor.

Required clearances:

There must be a 5-1/2” (14 cm) minimum (7”/17.8 cm

recommended) clearance between any object and the Front

and Rear covers in the event service is needed. A minimum of

3” (7.6 cm) clearance with the sides of the water heater is also

recommended for service access.

A 14” (35.6 cm) minimum clearance is required to remove the

filter for cleaning. The hot and cold water plumbing

and electrical connections must not interfere with

the removal of the filter.

Condensation drain

The unit has a condensate drain; therefore a drain must be

available in close proximity to the unit. The drain must be no

higher than 36” (91.4 cm) above the floor (laundry drain is

acceptable).

If no drain is available, then a common condensate pump with

a capacity no less than 1 gallon (3.8 L)/day must be purchased

from a local builder supply store and installed.

B

A

Route to open drain. Line

should be at least 3/4”

(1.9 cm) ID and pitched

for proper drainage.

14” (35.6 cm)

5-1/2”

(14 cm)

5-1/2”

(14 cm)