beautypg.com

Troubleshooting – refrigeration circuit – Greenheck Fan Energy Recovery Ventilator with Heat Pump 473501 User Manual

Page 32

background image

32

Model ERCH-HP Energy Recovery Unit

Troubleshooting – Refrigeration Circuit

Symptom

Possible Cause

Corrective Action

Compressor starts

but cuts out on high

pressure switch

High pressure

activates at

600 PSIG for

R410A

Refrigerant overcharge.

Check pressures, charge by subcooling.

Condenser fan motor defective.

Check fan motor.

Condenser coil inlet obstructed or dirty.

Check coil and inlet clearances.

Air or non-condensables in system.

Check high side equalized pressure reading with
equivalent outdoor temperature.

Defective high pressure switch.

Replace.

Restriction in discharge or liquid line.

Check refrigerant line pressures, check thermal
expansion valves.

Condensing fan relay not pulling in.

Replace.

Reheat valve and bypass valve not opening.

Check valves or valve circuit board.

Compressor cuts out

on thermal overload

Low voltage.

Check voltage.

Sustained high discharge pressure.

Check running amperage and conditions described
under ‘Low suction pressure’ symptoms.

High suction and discharge pressures.

Check thermal expansion valve setting, check for
air in system.

Defective compressor overload.

If compressor is hot, allow compressor to cool for
two hours. Recheck for open circuit.

Improper refrigerant charge.

Check subcooling.

Improperly wired.

Review wiring schematics.

Loose wiring.

Check all connections and wires.

Defective start relay.

Replace relay.

Motor windings damaged.

Verify amp draw.

Compressor hums,

but will not start

Improperly wired.

Review wiring schematics.

Low line voltage.

Check voltage.

Loose wiring.

Check all connections.

Defective start or run capacitor.

Check run capacitor for compressor and fan motor.

Defective relay start.

Replace relay.

Motor winding damaged.

Verify amp draws.

Internal compressor mechanical damage.

Replace.

Always have a completed Pre Start-Up Checklist and Unit Start-Up Checklist prior to requesting parts or service information.