Model ERCH-HP Energy Recovery Unit
Refrigeration System Schematic
Typical Operating Conditions
Location
Refrigerant State
Temperature
Pressure
Superheat/Subcool
Cooling
Mode /
Refrigerant
Properties
Before water-to-refrigerant
heat exchanger
Hot Vapor
150°F
330 PSIG
50°F Superheat
After water-to-refrigerant
heat exchanger
Warm Liquid
85°F
330 PSIG
15°F Subcool
After Thermostatic
Expansion Valve
Saturated Liquid-
Vapor mix
-45°F
144 PSIG
After Airside Coil
Cold Vapor
55°F
145 PSIG
10°F Superheat
Water entering the coaxial heat exchanger is warmed by the heat it absorbs from the refrigerant and leaves about
10°F warmer.
Location
Refrigerant State
Temperature
Pressure
Superheat/Subcool
Heating
Mode /
Refrigerant
Properties
Before Airside Coil
Hot Vapor
130°F
250 PSIG
50°F Superheat
After Airside Coil
Warm Liquid
65°F
250 PSIG
15°F Subcool
After Thermostatic
Expansion Valve
Saturated Liquid-
Vapor mix
-35°F
120 PSIG
After water-to-refrigerant
heat exchanger
Cold Vapor
45°F
120 PSIG
10°F Superheat
Water entering the coaxial heat exchanger is cooled because of the heat being absorbed by the refrigerant and
leaves about 6
°F warmer.