Sq 70-75 - direct drive – Greenheck Fan SQ User Manual
Page 12

1
(25)
12
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound ratings shown are loudness values in fan sones at 1.5 m (5 feet) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation
type B: free inlet hemispherical fan sone levels.
0
100
200
300
400
500
600
0
10
20
30
40
50
60
70
80
90
100
110
0
50
100
150
200
250
300
350
400
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
Static Pr
essur
e in. wg
cfm
m
3
/hr
Static Pr
essur
e Pa
SQ-75-D
SQ-75-G
SQ-75-E
SQ-70-E
SQ-70-G
SQ-70-D
RPM
Density 0.075 lb/ft
3
Damper size = 9 x 9
(229 x 229)
Unit weight** = 26
(12)
Housing thickness = 20 ga
Outlet velocity = 1.828 x cfm
Dimensions shown in inches (millimeters) and weight is
shown in pounds (kilograms).
*May be greater depending on motor.
**Weight shown is largest cataloged Open Drip Proof motor.
SQ 70-75 - Direct Drive
Model Number
Motor
HP
Fan
RPM
CFM / Static Pressure in Inches wg
0
0.1
0.125
0.15
0.2
0.25
0.3
0.35
0.375
0.4
SQ-70-E
1/100
1050
CFM
212
140
118
86
BHP
0.008
0.009
0.009
0.009
Sones
2.7
1.7
1.5
1.5
SQ-70-G
1/50
1300
CFM
262
204
190
176
139
77
BHP
0.015
0.018
0.018
0.018
0.017
0.015
Sones
4.1
3.4
3.3
3.1
2.9
2.5
SQ-70-D
1/30
1550
CFM
313
265
252
240
216
189
155
99
67
BHP
0.026
0.029
0.03
0.03
0.03
0.03
0.029
0.026
0.025
Sones
5.6
5.2
5.1
5.1
4.9
4.7
4.5
4.2
4.0
SQ-75-E
1/100
1050
CFM
241
167
146
123
BHP
0.01
0.011
0.011
0.01
Sones
3.6
2.9
2.8
2.6
SQ-75-G
1/50
1300
CFM
298
239
224
209
176
133
BHP
0.019
0.021
0.021
0.021
0.02
0.019
Sones
4.1
3.7
3.7
3.7
3.6
3.5
SQ-75-D
1/30
1550
CFM
356
306
294
281
256
229
201
164
137
99
BHP
0.032
0.034
0.035
0.035
0.035
0.035
0.034
0.033
0.032
0.029
Sones
6.1
5.5
5.4
5.3
5.1
4.9
4.9
4.8
4.8
4.8
13
(330)
12
(305)
*8
7
⁄
8
(225)
12
(305)