GSW 72090 User Manual
Page 19
if not eliminate water odour problems. The water supply sys-
tem may require special filtration equipment from a water
conditioning company to successfully eliminate all water
odour problems.
Artificially softened water is exceedingly corrosive because
the process substitutes sodium ions for magnesium and cal-
cium ions. The use of a water softener may decrease the life
of the water heater tank. The anode should be inspected
periodically. If the anode is more than 50% depleted, the
anode should be replaced.
VI) MAINTENANCE
Draining and Flushing
It is recommended that the tank be drained and flushed
every 6 months to remove sediment which may buildup dur-
ing operation. The water heater should be drained if being
shut down for extended periods of time. To drain the tank,
perform the following steps:
1. Turn off the gas to the water heater with the manual gas
shut-off valve.
2. Close the cold water inlet valve.
3. Open a nearby hot water faucet.
4. Connect a hose to the drain valve and terminate it to an
adequate drain.
Note: The drain hose should be rated for at least 94°C
(200°F). If the drain hose does not have this rating, open the
cold water inlet valve and nearby hot faucet until the water
is no longer hot.
5. Open the water heater drain valve and allow all the
water to drain from the tank. Flush the tank with water
as needed to remove sediment.
6. Close the drain valve, refill the tank, and restart the
heater as directed under “Operating Instructions”. If the
water heater is going to be shut down for an extended
period, the drain valve should be left open.
Important: Condensation may occur when refilling tank and
should not be confused with a tank leak.
The installation and maintenance of the water heater must
comply with all of the instructions described in sections I to
IX of this manual. Water heater failure that is a result of the
heating system is not covered by warranty.
The following maintenance procedures are for the Flame
Guard
TM
safety system components and should be per-
formed by a qualified service technician.
Replacement parts (see Figures 20 & 21) may be ordered
through your local distributor. When ordering replacement
parts, always have the following information ready:
1. Model, serial and product number.
2. Type of gas.
3. Item number.
4. Parts description.
Periodic Inspection
Periodically a visual inspection should be made of the vent-
ing and air supply system, piping systems, main burner,
pilot burner and flame arrester.
Check the water heater for the following:
1. Obstructions, damage or deterioration in the venting
system. Make sure the ventilation and combustion air
supplies are not obstructed.
2. Build-up of soot and carbon on the main burner and
pilot burner. Check for a soft blue flame.
3. Leaking or damaged water and gas piping.
4. Presence of flammable or corrosive materials in the
installation area.
5. Presence of combustible materials near the water
heater.
6. Presence of debris on the outside of the flame arrester.
See note below.
– 19 –