OPERATING DATA

QT048

RATING: All three phase units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings
apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is
no overload capability for this rating. Ratings are in accordance with ISO-3046-1, BS5514, and DIN6271. Maximum wattage and current are subject
to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition. Design and specifications are subject
to change without notice.
KW rating is based on LPG Fuel and may derate with natural gas.

QT048

kW RATING

48

ENGINE SIZE

4.2 Liter V6

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

kW - LP

Amps

kW - NG

Amps

CB Size

120/208V, 3-phase, 0.8 pf

48

166

46

160

175

120/240V, 3-phase, 0.8 pf

48

144

46

138

150

277/480V, 3-phase, 0.8 pf

48

72

46

69

80

GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%

Single phase or 208 3-phase

100

480V 3-phase

110

ENGINE FUEL CONSUMPTION

(Natural Gas) (Propane)

Natural Gas

Propane

(ft

3

/hr.)

(gal/hr.)

cu ft/hr

Exercise cycle

88

0.94

34.4

25% of rated load

205

2.23

81

50% of rated load

370

4.03

147

75% of rated load

516

5.62

204

100% of rated load

661

7.20

261

ENGINE COOLING

Air flow

(inlet air including alternator and combustion air)

ft

3

/min.

2,460

System coolant capacity

US gal.

3.0

Heat rejection to coolant

BTU/hr.

165,000

Max. operating air temp. on radiator

°C (°F)

60 (150)

Max. ambient temperature

°C (°F)

50 (140)

COMBUSTION AIR REQUIREMENTS

Flow at rated power 60 Hz

cfm

235

SOUND EMISSIONS IN DBA

Exercising at 7 meters

60

Normal operation at 7 meters

65

EXHAUST

Exhaust flow at rated output 60 Hz

cfm

395

Exhaust temp. at muffler outlet

°F

1100

ENGINE PARAMETERS

Rated synchronous RPM

60 Hz

1800

HP at rated KW

60 Hz

75

POWER ADJUSTMENT FOR AMBIENT CONDITIONS

Temperature Deration

3% for every 10 °C above - °C

25

1.65% for every 10 °F above - °F

77

Altitude Deration

1% for every 100 m above - m

183

3% for every 1000 ft. above - ft.

600