Netpro 19” model : 600 1000 1500, General, Ge digital energy – GE 600 - 1500 VA User Manual
Page 14: 8 - specifications
OPM_NPE_19X_600_1K5_2GB_V030
13
GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
g
GE Digital Energy
NetPro 19” model
:
600
1000
1500
Ratings
Voltage Amperes (VA)
:
600
1000
1500
with computer type load
Watts (W)
:
360
600
900
with resistive load
Input thermal circuit breaker (A)
:
5
5
7
Input fuse (A)
:
8
8
10
Input converter
AC input voltage
:
220 - 240 V
AC input voltage range
:
100% load: 187 - 264 V
70% load: 120 - 264 V
input >264 Vac: UPS switches to battery operation
input >312 Vac: UPS shuts down, manual restart required
Minimum start-up AC voltage
:
187 V (at any load)
Input current waveform
:
sinusoidal
conform or better than EN 61000-3-2 (IEC 555-2)
Input current (A) at nom. inp. volt.
:
2.0
3.3
5.0
Input power factor
:
1
Input frequency range
:
45 - 66 Hz
Inrush current
:
none
Output converter
AC output voltage
:
230 V (suitable for 220 - 240 V loads)
AC output voltage tolerance
:
± 2%
Output frequency
:
50 or 60 Hz, front selectable
Output frequency range
:
nominal ± 0.15% unless synchronized to the mains
Output waveform
:
sine wave
Harmonic distortion
:
< 2% (typical 1.5%) with linear load
Power factor
:
0.6 (0.7 at 90% load)
Crest factor (peak to RMS current)
:
suitable for loads with c.f. up to 6:1
Capacity appliance outlets
:
max. 10 A per outlet
Bypass
AC input voltage range
:
195 - 264 V
Frequency tracking rate
:
2 Hz/sec.
Frequency tracking range
:
nominal ± 10%
Phase difference
:
< 7º
Typical transfer time, msec
:
4
Overload capability
:
Fully protected against overload and short circuits
Overload behaviour (battery operation)
:
110% during 5 minutes; 150% during 5 seconds
Overload behaviour during
:
depends on rating of thermal circuit breaker
bypass operation
typical: 125% of TCB value for 200 seconds
200% of TCB value for 10 seconds
300% of TCB value for 4 seconds
Batteries (ratings given for 25ºC)
Nominal voltage (Vdc)
:
24
36
48
Number of 7 Ah batteries
:
2
3
4
Type
:
sealed lead acid, maintenance free
Service life
:
up to 6 years (depending on use)
Recharge current
:
1.5 A
Battery recharge time
(batt. discharged at 100% load)
:
1.5 hours for 90% capacity, std battery
Runtime in minutes
at typical load (75%)
:
12
12
10
VA/Watts
100/60
:
64
104
124
200/120
:
34
54
71
400/240
:
15
27
36
600/360
:
9
15
24
1000/600
:
-
9
12
1500/900
:
-
-
6
General
Weight without battery drawer (kg)
:
14
14
14
Weight with battery drawer (kg)
:
19
22
24
Dimensions (hxwxd, mm)
:
133.5 (3HU) x 450 (19”) x 440
Depth required in 19” rack (mm)
:
420 (without connectors)
Enclosure / protection
:
steel - plastic / IP20
Environment
Safety
:
EN 50091-1-1, EN 60950, IEC 950
Electromagnetic compatibility
:
EN 50091-2
Ambient temperature
:
-10 to +40ºC
Audible noise at 1 meter
:
< 45 dB(A), load and temperature dependent
Max. relative humidity
:
95% (non-condensing)
8 - Specifications