beautypg.com

Netpro 19” model : 600 1000 1500, General, Ge digital energy – GE 600 - 1500 VA User Manual

Page 14: 8 - specifications

background image

OPM_NPE_19X_600_1K5_2GB_V030

13

GE DE NetPro 19” 600-1500: User manual 3.0 (GB)

g

GE Digital Energy

NetPro 19” model

:

600

1000

1500

Ratings

Voltage Amperes (VA)

:

600

1000

1500

with computer type load

Watts (W)

:

360

600

900

with resistive load

Input thermal circuit breaker (A)

:

5

5

7

Input fuse (A)

:

8

8

10

Input converter

AC input voltage

:

220 - 240 V

AC input voltage range

:

100% load: 187 - 264 V

70% load: 120 - 264 V

input >264 Vac: UPS switches to battery operation

input >312 Vac: UPS shuts down, manual restart required

Minimum start-up AC voltage

:

187 V (at any load)

Input current waveform

:

sinusoidal

conform or better than EN 61000-3-2 (IEC 555-2)

Input current (A) at nom. inp. volt.

:

2.0

3.3

5.0

Input power factor

:

1

Input frequency range

:

45 - 66 Hz

Inrush current

:

none

Output converter

AC output voltage

:

230 V (suitable for 220 - 240 V loads)

AC output voltage tolerance

:

± 2%

Output frequency

:

50 or 60 Hz, front selectable

Output frequency range

:

nominal ± 0.15% unless synchronized to the mains

Output waveform

:

sine wave

Harmonic distortion

:

< 2% (typical 1.5%) with linear load

Power factor

:

0.6 (0.7 at 90% load)

Crest factor (peak to RMS current)

:

suitable for loads with c.f. up to 6:1

Capacity appliance outlets

:

max. 10 A per outlet

Bypass

AC input voltage range

:

195 - 264 V

Frequency tracking rate

:

2 Hz/sec.

Frequency tracking range

:

nominal ± 10%

Phase difference

:

< 7º

Typical transfer time, msec

:

4

Overload capability

:

Fully protected against overload and short circuits

Overload behaviour (battery operation)

:

110% during 5 minutes; 150% during 5 seconds

Overload behaviour during

:

depends on rating of thermal circuit breaker

bypass operation

typical: 125% of TCB value for 200 seconds

200% of TCB value for 10 seconds

300% of TCB value for 4 seconds

Batteries (ratings given for 25ºC)

Nominal voltage (Vdc)

:

24

36

48

Number of 7 Ah batteries

:

2

3

4

Type

:

sealed lead acid, maintenance free

Service life

:

up to 6 years (depending on use)

Recharge current

:

1.5 A

Battery recharge time

(batt. discharged at 100% load)

:

1.5 hours for 90% capacity, std battery

Runtime in minutes

at typical load (75%)

:

12

12

10

VA/Watts

100/60

:

64

104

124

200/120

:

34

54

71

400/240

:

15

27

36

600/360

:

9

15

24

1000/600

:

-

9

12

1500/900

:

-

-

6

General

Weight without battery drawer (kg)

:

14

14

14

Weight with battery drawer (kg)

:

19

22

24

Dimensions (hxwxd, mm)

:

133.5 (3HU) x 450 (19”) x 440

Depth required in 19” rack (mm)

:

420 (without connectors)

Enclosure / protection

:

steel - plastic / IP20

Environment

Safety

:

EN 50091-1-1, EN 60950, IEC 950

Electromagnetic compatibility

:

EN 50091-2

Ambient temperature

:

-10 to +40ºC

Audible noise at 1 meter

:

< 45 dB(A), load and temperature dependent

Max. relative humidity

:

95% (non-condensing)

8 - Specifications