beautypg.com

Ge digital energy, 5 - optional features 6 - maintenance – GE 600 - 1500 VA User Manual

Page 11

background image

OPM_NPE_19X_600_1K5_2GB_V030

10

GE DE NetPro 19” 600-1500: User manual 3.0 (GB)

g

GE Digital Energy

Apart from the options described in 4.2 and 4.3 the following options are possible:

5.1

Extended Runtime (NetPro 19” 1000)

Extended runtime can be obtained by connecting a separate battery extension pack to the UPS. In this

case the UPS must be informed about the new total battery capacity to allow a reliable recalculation of the

available runtime (please contact your dealer). Dependent of the charge condition of the new batteries the

new runtime calculations may temporarily be unreliable.

The additional batteries increase the recharging time for the unit, all other operational information is the

same as for standard models. It is not allowed to connect an external charger to the UPS!

5.2

PowerFLAG SerVICe Box for Modem Connection

If you connect the PowerFLAG SerVICe Box between the communication port of the UPS and a modem,

a programmed number can be dialed in case of a UPS alarm. It also allows service personnel to dial in

and check the status of the UPS to perform remote diagnostics. This way service costs, specially in

remote areas, can be reduced considerably.

6.1

General

The UPS is virtually maintenance free: take care of proper environmental conditions and keep air

inlets/outlets free of dust. Please read 2.1.

6.2

Batteries

6.2.1

General

The service life of the battery is from 3 to 6 years, depending on the operating temperature and on the

number of discharge cycles.

As a healthy battery is critical to the performance of the UPS, an automatic quick battery test is performed

regularly to ensure failsafe operation (see section 3.5). When the condition of the battery is critical, a

'replace battery' alarm will be activated (see 3.3.9). Replace the batteries as soon as possible. See 6.6.2.

NOTE: under certain circumstances a manual battery test can result in a false alarm: please see 3.5

'quick battery test'.

6.2.2

Battery replacement

-

WARNING:

first read the safety rules in section 1.2.

- When replacing the batteries, use the same number and voltage(V)/capacity(Ah).

- Proper disposal or recycling of the batteries is required. Refer to your local codes for disposal

requirements.

- Never dispose of batteries in a fire: they may explode.

- Do not open or mutilate batteries: their contents (electrolyte) may be extremely toxic. If exposed to

electrolyte, wash immediately with plenty of water.

- Avoid charging in a sealed container.

- Never short circuit batteries. When working with batteries, remove watches, rings or other metal

objects, and only use insulated tools.

Battery replacement procedure: see next page

5 - Optional Features

6 - Maintenance