beautypg.com

Xpanded, Eating, Roduct – Goodman Mfg SS-GSH10C User Manual

Page 10: Pecifications

background image

p

RoduCt

S

pECifiCationS

p

RoduCt

S

pECifiCationS

10

www.goodmanmfg.com

SS-GSH10C

E

xpandEd

H

EatinG

d

ata

GSH100903A* / AR090

Outdoor Ambient Temperature

65°F

60°F

55°F

50°F

47°F

45°F

40°F

35°F

30°F

25°F

20°F

17°F

15°F

10°F

5°F

0°F

-5°F

-10°F

MBh

103.1

97.6

91.8

85.9

82.0

79.5

73.8

68.1

66.0

61.0

56.1

53.0

51.0

45.8

40.6

35.4

30.2

24.8

∆T

33.1

31.4

29.5

27.6

26.4

25.5

23.7

21.9

21.2

19.6

18.0

17.0

16.4

14.7

13.1

11.4

9.7

8.0

kW

8.04

7.89

7.74

7.59

7.50

7.44

7.29

7.14

7.48

7.32

7.16

7.06

7.00

6.83

6.67

6.51

6.34

6.18

Amps

24.4

22.6

21.1

19.8

19.1

18.7

17.6

16.7

16.0

15.3

14.5

14.2

14.0

13.3

12.4

11.6

10.7

9.6

COP

3.75

3.62

3.47

3.31

3.20

3.13

2.96

2.79

2.58

2.44

2.30

2.20

2.14

1.96

1.78

1.59

1.39

1.17

EER

12.8

12.4

11.9

11.3

10.9

10.7

10.1

9.5

8.8

8.3

7.8

7.5

7.3

6.7

6.1

5.4

4.8

4.0

Hi PR

244

234

225

215

210

206

198

190

182

174

167

163

160

154

148

142

137

132

Lo PR

72

66

62

57

54

52

48

43

38

34

30

28

27

23

20

17

15

11

GSH100903B* / AR090

Outdoor Ambient Temperature

65°F

60°F

55°F

50°F

47°F

45°F

40°F

35°F

30°F

25°F

20°F

17°F

15°F

10°F

5°F

0°F

-5°F

-10°F

MBh

105.8 100.1

94.2

88.1

84.1

81.5

75.7

69.8

64.1

59.1

54.5

51.4

49.5

44.4

39.4

34.3

29.3

24.0

∆T

32.1

30.4

28.6

26.7

25.5

24.8

23.0

21.2

19.5

18.0

16.5

15.6

15.0

13.5

12.0

10.4

8.9

7.3

kW

8.03

7.88

7.73

7.58

7.49

7.42

7.28

7.12

7.95

7.77

7.59

7.49

7.42

7.24

7.06

6.88

6.70

6.52

Amps

30.2

28.1

26.4

24.9

24.1

23.7

22.4

21.4

20.5

19.7

18.8

18.4

18.2

17.4

16.3

15.5

14.4

13.2

COP

3.85

3.72

3.57

3.40

3.29

3.21

3.05

2.87

2.36

2.23

2.10

2.01

1.95

1.80

1.63

1.46

1.28

1.08

EER

13.2

12.7

12.2

11.6

11.2

11.0

10.4

9.8

8.1

7.6

7.2

6.9

6.7

6.1

5.6

5.0

4.4

3.7

Hi PR

268

257

247

236

230

226

217

209

200

191

183

179

176

169

162

156

150

145

Lo PR

72

67

63

57

54

52

48

43

39

34

30

28

27

23

20

17

15

11

GSH101203A* / AR120

Outdoor Ambient Temperature

65°F

60°F

55°F

50°F

47°F

45°F

40°F

35°F

30°F

25°F

20°F

17°F

15°F

10°F

5°F

0°F

-5°F

-10°F

MBh

132.6 125.5 118.2 110.5 105.5 102.2

95.0

87.6

85.4

78.8

72.5

68.5

66.0

59.2

52.5

45.8

39.0

32.0

∆T

30.7

29.1

27.4

25.6

24.4

23.7

22.0

20.3

19.8

18.2

16.8

15.9

15.3

13.7

12.1

10.6

9.0

7.4

kW

10.41 10.21 10.01

9.81

9.70

9.62

9.43

9.23

9.69

9.47

9.26

9.13

9.05

8.83

8.62

8.41

8.19

7.98

Amps

28.3

26.2

24.5

23.0

22.1

21.7

20.4

19.3

18.4

17.6

16.7

16.3

16.1

15.2

14.1

13.3

12.2

10.9

COP

3.73

3.60

3.45

3.29

3.18

3.11

2.95

2.78

2.58

2.44

2.29

2.20

2.13

1.96

1.78

1.59

1.40

1.17

EER

12.7

12.3

11.8

11.3

10.9

10.6

10.1

9.5

8.8

8.3

7.8

7.5

7.3

6.7

6.1

5.4

4.8

4.0

Hi PR

221

212

203

195

190

186

179

172

165

157

151

147

145

139

134

128

124

120

Lo PR

66

62

58

53

50

48

44

39

36

32

28

26

25

21

18

15

13

11

High pressure is measured at the suction service valve ( the larger valve).

Amps = Outdoor unit amps (comp.+fan)

Low pressure is measured at the gauge port connection.

kW = Total system power