4 generator tests under load – Generac Power Systems 04635-0 User Manual

Page 9

background image

Generac

®

Power Systems, Inc.

7

3.4

GENERATOR TESTS UNDER LOAD

1. Set the generator's main circuit breaker to its

OFF or OPEN position.

2. Manually actuate the transfer switch main

contacts to their EMERGENCY (STANDBY)
position. Refer to Manual Operation.

3. To start the generator, set the AUTO-OFF-

MANUAL switch to MANUAL. When engine starts,
let it stabilize for a few minutes.

4. Turn the generator's main circuit breaker to its

ON or CLOSED position. The generator now
powers all LOAD circuits. Check generator
operation under load as follows:

Turn ON electrical loads to the full rated
wattage/amperage capacity of the generator.
DO NOT OVERLOAD.

With maximum rated load applied, check
voltage and frequency across transfer switch
terminals E1 and E2. Voltage should be
greater than 230 volts; frequency should be
greater than 59 Hz.

Let the generator run under rated load for at
least 30 minutes. With unit running, listen for
unusual noises, vibration, overheating, etc.,
that might indicate a problem.

5. When checkout under load is complete, set main

circuit breaker of the generator to its OFF or
OPEN position.

6. Let the generator run at no-load for several

minutes. Then, shut down by setting the AUTO-
OFF-MANUAL switch to its OFF position.

7. Move the switch's main contacts back to their

utility position. For example, load connected to
utility power supply. Refer to Manual Operation.
Handle and operating lever of transfer switch
should be in down position.

8. Turn on the utility power supply to transfer

switch, using whatever means provided (such as
a utility main line circuit breaker). The utility
power source now powers the loads.

9. Set the generator's AUTO-OFF-MANUAL switch to

its AUTO position. The system is now set for fully
automatic operation.

Section 3 — Operation

Generac GTS “W” Type Transfer Switch