WARNING:
Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness.
Never operate the UV-Aire
™
Air Purifying System out of the plenum. Avoid touching the glass portion of the lamp with your hands.
MAINTENANCE
WARNING:
Disconnect power to the transformer before commencing inspection and cleaning.
NOTE:
Wear disposable, non-absorbent protective gloves prior to inspection procedure in case of accidental
breakage of glass.
We recommend inspecting and cleaning the lamp at least every 6 months. Frequency depends upon the
1.
environment. Such as: the type of air filter, duration of use and replacement cycle.
To maintain maximum output intensity, replace the UV-Aire lamp annually. The lamp should operate
2.
continuously for maximum lamp life and light effectiveness.