Appendix B.4.
How to build a script file that tests a customer log.
The following brief notes are intended for configuration engineers who are expected to be familiar
with the FieldServer.
•
Take the hex log file and convert to ASCII using special chars (this is an option of the log file
converter)
•
Choose a response line from near the end of the log (most recent). Check the line is complete.
•
Place the line inside an INI file. Make the following changes
•
Replace [NP] with [FF]
•
Replace [SP] with a space
•
Replace [NULL] with a space.
•
Use the following files as a guide.
Client.csv
Data_Arrays
Data_Array_Name, Data_Format, Data_Array_Length
DA_D1_01,
Float,
500
Connections
Port ,
Parity, Baud, Data_Bits, Stop_Bits, Handshaking, Protocol,
Timeout,
Print_storage_locations
P1,
None, 9600, 8,
1,
None,
CarrierDP, 60s,
Yes
Nodes
Node_Name, Node, Protocol, Port
Node_A ,
1,
CarrierDP, P1
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Length, Scan_Interval,
CMD_GP_01,
DA_D1_01,
0,
Rdbc,
Node_A,
202,
5.0s
Server.csv
Data_Arrays
Data_Array_Name, Data_Format, Data_Array_Length
TABLE_DISPLAY,
Float,
500
Connections
Port ,
Parity, Baud, Data_Bits, Stop_Bits, Handshaking, Protocol,
P1,
None,
1200, 8,
1,
None,
CarrierDP,
Nodes
Node_Name, Node, Protocol,
Node_A ,
1,
CarrierDP,