4.4.2 Driver Specific Map Descriptor Parameters
Column Title
Function
Legal Values
Node_Name
Name of Node to fetch data
from
One of the node names
specified in “Client Node
Descriptor” above
Data_Array_Offset
Position in the data array to
which data should start being
written.
0, 1 , 2 , 3
Length
Length of Map Descriptor. The
length is required to help the
driver validate the CSV file.
Set the length to a multiple of
16. The multiple should be the
maximum area number.
1 – 1280
Address
Starting address of read block
0
Driver specific keywords
The following parameters apply only to the AMI ACM driver.
ATMI_Data*
Used to specify which
component of the gas data
structure to store.
You will need one map
descriptor for each
component that you are
interested in storing.
See section 6.9 for more
info.
Slot-alarm,
Slot-warning,
Slot-combo
Slot-values
Port-alarm,
Port-warning,
Port-combo
Gas-value, (== Port-values)
Current-Port
Current-Slot
Malfunctions
4.4.3 Timing
Parameters
Column Title
Function
Legal Values
Scan_Interval
Rate at which data is polled
>0.1s