Example

// Data Arrays
//
Data_Arrays
Data_Array_Name,

Data_Format, Data_Array_Length

DA_AI_01,

UInt16,

200

DA_AO_01,

UInt16,

200

DA_DI_01,

Bit,

200

DA_DO_01,

Bit,

200


4.2 Client Side Connections

Section Title

Connections

Column Title

Function

Legal Values

Port

Specify which port the device is
connected to the FieldServer

P1-P8, R1-R2

Baud*

Specify baud rate

110 – 115200, standard baud
rates only

Parity*

Specify parity

Even, Odd, None, Mark, Space

Data_Bits*

Specify data bits

7, 8

Stop_Bits*

Specify stop bits

1

Protocol

Specify protocol used

ATMI

Handshaking*

Specify hardware handshaking

RTS, RTS/CTS, None

Poll Delay*

Time between internal polls

0-32000 seconds
default 1 second

Timeout

Specifies the amount of time that
may pass between complete
data screens. If this time expires
a timeout error is produced but
the processing of data is not
affected. The port is not cleared
and gas data is not reset.

This value should provide a
margin over the time configured
between samples in the
CONFIG.DAT profile of the
ACM unit.

IC_Timeout

This parameter is used in a way
that is different to most
FieldServer driver applications.
In this case of this driver it
specifies the maximum amount
of time that may pass between
the driver receiving an incoming
character. If the time is
exceeded then an error is
produced but note that the error
has no other effect on the driver.
The port is not cleared and gas
data is not reset.

This value (specified in
seconds) should be set allow a
margin between time stamp
messages from the ACM unit.