COOlING ONlY ROOM AIR CONDITIONeRS: TROUBleSHOOTING TIPS

n

o

it

c

A

e

s

u

a

C

e

l

b

i

s

s

o

P

m

e

l

b

o

r

P

Water “spitting”

into room

Sublimation:
When unconditioned saturated,
outside air mixes with conditioned

air, condensation forms on the
cooler surfaces

Ensure that foam gaskets are installed in
between window panes & in between the
unit & the sleeve. Also, ensure that fresh
air/exhaust vents (on applicable models) are in

the closed position & are in tact

Downward pitch of installation is
too steep towards back of unit

Follow installation instructions to ensure that
downward pitch of installed unit is no less than
1/4” & no more than 3/8”

Restricted coil or dirty fi lter

Clean & advise customer of periodic cleaning
& maintenance needs of entire unit

n

o

it

c

A

e

s

u

a

C

e

l

b

i

s

s

o

P

m

e

l

b

o

r

P

Excessive

moisture

Insuffi cient air circulation thru area
to be air conditioned

Adjust louvers for best possible air circulation

n

o

it

i

s

o

p

r

e

v

a

S

y

e

n

o

M

n

i

e

t

a

r

e

p

O

t

i

n

u

d

e

z

i

s

r

e

v

O
Inadequate vapor barrier in building

structure, particularly fl oors

Advise customer

n

o

it

c

A

e

s

u

a

C

e

l

b

i

s

s

o

P

m

e

l

b

o

r

P

T-stat or

thermistor

short cycles

Defective thermistor

Replace thermistor or electronic control board

T-stat differential too narrow

Replace t-stat

Plenum gasket not sealing,
allowing discharge air to short
cycle t-stat

Check gasket. Reposition or replace as
needed

Restricted coil or dirty fi lter

Clean & advise customer of periodic cleaning
& maintenance needs of entire unit

n

o

it

c

A

e

s

u

a

C

e

l

b

i

s

s

o

P

m

e

l

b

o

r

P

Prolonged off

cycles (automatic

operation)

Heat anticipator (resistor) wire
disconnected at t-stat or system
switch

Refer to appropriate wiring diagram

Heat anticipator (resistor) shorted or

open

Disconnect plus from outlet. Remove resistor
from bracket. Insert plug & depress “COOL”
& “FAN AUTOMATIC” buttons. Place t-stat to
warmest setting. Feel resistor for temperature.
If no heat, replace resistor

Partial loss of charge in t-stat bulb
causing a wide differential

Replace t-stat

Defective thermistor

Replace thermistor or electronic control board

n

o

it

c

A

e

s

u

a

C

e

l

b

i

s

s

o

P

m

e

l

b

o

r

P

Outside water

leaks

Evaporator drain pan cracked or
obstructed

Repair, clean or replace as required

Water in compressor area

Detach shroud from pan & coil. Clean &
remove old sealer. Reseal, reinstall & check

Obstructed condenser coil

Use pressure wash or biodegradable cleaning
agent to clean

Fan blade/slinger ring improperly
positioned

Adjust fan blade to 1/2” of condenser coil fi n

pack