COOlING ONlY ROOM AIR CONDITIONeRS: TROUBleSHOOTING TIPS

n

o

it

c

A

e

s

u

a

C

e

l

b

i

s

s

o

P

m

e

l

b

o

r

P

Unit does not run

Fuse blown or circuit tripped

Replace fuse, reset breaker. If repeats, check
fuse or breaker size. Check for shorts in unit
wiring & components

Power cord not plugged in

Plug it in

System switch in “OFF” position

Set switch correctly

Inoperative system switch or open

control board

Test for continuity

Loose or disconnected wiring at
switch, control board or other com-

ponents

Check wiring & connections. Reconnect per
wiring diagram

n

o

it

c

A

e

s

u

a

C

e

l

b

i

s

s

o

P

m

e

l

b

o

r

P

Evaporator coil

freezes up

Dirty fi

l

a

u

n

a

M

s

’r

e

n

w

O

n

i

d

e

d

n

e

m

m

o

c

e

r

s

a

n

a

e

l

C

r

e

tl

Restricted airfl ow

Check for dirty or obstructed coil. Use
pressure wash or biodegradable cleaning
agent to clean

Inoperative t-stat or thermistors

Test for continuity

Short of refrigerant

De-ice coil & check for leak

Inoperative fan motor

Test fan motor & replace if inoperative

Partially restricted capillary tube

De-ice coil. Check temp. differential (delta T)
across coil. Touch test coil return bends for
same temp. Test for low running current

n

o

it

c

A

e

s

u

a

C

e

l

b

i

s

s

o

P

m

e

l

b

o

r

P

Compressor runs

continually & does

not cycle off

Excessive heat load

Unit undersized. Test cooling performance &
replace with larger unit if needed

Restriction in line

Check for partially iced coil & check
temperature split across coil

Refrigerant leak

Check for oil at silver soldered connections.
Check for partially iced coil. Check split across
coil. Check for low running amperage

T-stat contacts stuck

Check operation of t-stat. Replace if contacts
remain closed.

T-stat incorrectly wired

Refer to appropriate wiring diagram

Thermistor shorted

Replace thermistor or electronic control board

n

o

it

c

A

e

s

u

a

C

e

l

b

i

s

s

o

P

m

e

l

b

o

r

P

T-stat does not

turn unit off

T-stat contacts stuck

Disconnect power to unit. Remove cover
of t-stat & check if contacts are stuck. If so,
replace t-stat

T-stat set at coldest point

Turn to higher temp. setting to see if unit
cycles off

Incorrect wiring

Refer to appropriate wiring diagrams

Unit undersized for area to be
cooled

Refer to industry standard sizing chart

Defective thermistor

Replace thermistor or electronic control board