beautypg.com

Fedders FV95A090 User Manual

Page 44

background image

IF

AND

CHECK or REPAIR

Induced blower does

not energize

3 Flash code does not come on

1. Induced blower wiring.
2. Induced blower.

Induced blower does

not energize

3 Flash code does come on

1.

Pressure switch stuck closed.

2.

Pressure switch is mis-wired or jumpered.

Induced blower is

energized

2 Flash code does not come o n Wait for the pre-purge to expire.

2 Flash code

comes on

Induced blower turns off

1. Pressure

switch stuck in the open position.

2.

Pressure switch, tubing and wiring.

3.

Obstruction in furnace venting that is preventing proper combustion airflow.

Pre-purge time h as

expired

HSI element does not glow r ed

within 10 seconds.

1. Broken or damaged HSI element.
2. Broken or damaged HSI element leadwires.

HSI element i s glow-

ing red.

No other visible control system

action

Wait for HSI element warm up time to expire.

HSI element warm u p

time has expired a nd

main valve has been

energized.

Main valve does not light within

trial for ignition period

1. Induced blower moving main burner gas away from the HSI element.
2. Inlet gas pressure too low for main burner ignition.
3. Input line voltage too low to heat HSI element.
4. HSI element incorrectly positioned.
5. Clogged or incorrect main burner orifice.

Main burner

lights

within trial for ignition

period.

Main valve i s de-energized a t the

end of the trial for ignition period.
If main flame i s not sensed during

trial for ignition, system will shut o ff

HSI element and main gas flow,

then g o through another purge

period and initiate another ignition

trial. A total o f 4 ignition trials will

be attempted before the system

goes into lockout.

1. Line voltage to L1 terminal of integrated furnace control must be

120 volts with reference to furncace chassis.

2. Furnace must be reliably connected to earth ground.
3. Induced blower moving main burner flame away from the flame sensor rod.
4. Inlet gas pressure too low for proper flame sensing.
5. Flame sensor rod contaminated or in incorrect position.

Main burner stays o n

after the end of t he

trial for ignition p e-

riod.

Circulating fan is not turned on after

30-second time delay.

1. Wiring between system control and integrated furnace control.

Proper operation of integrated furnace control.

Main burner goes o ut

before thermostat call

for heat ends.

4 Flash code comes on

1.
2.

Open high limit switch.
High limit wiring in good condition and securely connected.

Main burner goes o ut

before thermostat call

for heat ends.

4 Flash code does not come on

Green LED off

1. Induced blower moving main burner flame away from flame sensor rod.

3.

Pressure switch has opened.

1.
2.

Open flame rollout switch
Rollout switch wiring in good condition
Broken or damaged blower

4.

Flame sensor rod ceramic or leadwire overheated.
Gas supply / flow reduced or interrupted.

5 Flash code comes

on.

TABLE 10 : GENERAL TROUBLESHOOTING INTEGRATED FAN CONTROL

42

3.

2.

2.

This manual is related to the following products: