Chapter 4 – Falcon SUP1.0K-1C User Manual
Page 12

CHAPTER 4
CHAPTER 4
Operation
1.
Turning The UPS On and Off
Depending on how the UPS was turned off, it may automatically turn 
on when the input plug is plugged in. If it does not turn on 
automatically, depress the control button located on the front panel 
for four seconds until the UPS turns on. To turn the UPS off press 
and hold the control button for five seconds or until the UPS turns 
off. UPS batteries will still continue to recharge after the UPS 
has turned off.
2.
UPS Self Test
Depressing the control button for one second while the UPS is 
turned on will initiate a self test sequence. 
3.
UPS Overload Condition
To ensure that your computer equipment will be protected during a 
utility failure, it is important to make sure that the maximum power 
required from the equipment is not over the rated capacity of the 
UPS. The LCD overload indicator will be displayed and an audible 
alarm will sound if the load is over 120% of the UPS's rated 
output. If the over load is greater than120% , the UPS will shut 
down immediately to protect the itself. After three seconds, if the 
overload is removed the UPS will automatically turn on again. If the 
overload is still present the UPS will turn off and stay off, requiring 
the UPS be manually restarted. Always correct any overload 
condition immediately.
4.
DC Start, Cold Start
To start the UPS when utility power is not available, press and hold 
down the control button twice for one second each time. The UPS 
will start up and run on its internal battery until discharged. If you do 
not depress the control button to turn the UPS off during battery 
operation, the UPS will automatically restart when utility voltage is 
reapplied. The UPS batteries should not be left discharged for long 
periods of time or battery damage may occur. 
Always reconnect the UPS to a utility source, turn the UPS on and 
allow the batteries to recharge for eight hours after the batteries 
have been fully discharged due to DC operation.
5.
Green Mode Function
The UPS is equipped with a Green mode function. If no load is 
present at the UPS output receptacles (no equipment connected or 
the load is less than 25 watts), the UPS will shut down within 12 
seconds. Should the utility AC be lost during the shut down, the UPS
will automatically restart and again shut down after another two 
minutes of no load being applied.
11
