FS-8700-83 Gamewell

Page 7 of 24

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]

Length

Length of Map Descriptor

Controls how many elements of the data
array are controlled by the map
descriptor.

1 – 1000

Address

This commonly used parameter has no
meaning for this driver. If specified it is
best set to zero.

0

Ckt

Specify the circuit number whose
message will get stored using this map
descriptor.

Use the keyword ‘Panel’ if the you wish
to store data from a panel. All messages
which do not contain the keyword ‘Ckt’ in
the action field are deemed to be panel
messages.

Valid panel numbers are 1-131

Panel , 1 ,2 , 3 …. 131

Dev

The starting device number for the map
descriptor. The length determines how
many devices can have their data stored
using this map descriptor.

Valid circuit numbers are 1-126 but this
driver allows a device number of zero to
allow for the storage of messages which
don’t specify a device number.

Ty

0 , 1 , 2 … 126

Clear_On_Reset

Yes,

No

Store_As*

Only relevant when the
Data_Type=’Dump’

This tells the driver to store ignored
messages in ASCII format or to dump
them in ASCII format in the error log.

AsciiLog
ASCII
Value

Gamewell_Func*

Only relevant when the function is write.

This parameter tell the driver what type
of command to send to the panel.

You should always Ack before you
silence the panel.

Reset
Ack
Silence

Timing Parameters

Column Title

Function

Legal Values

Scan_Interval

Rate at which data is polled

>0.1s